Firmware V3.00
05.08.2019
61/100
7.4 Mode of operation of the relay and transistor outputs
The table shows the mode of operation of the outputs for the separate controller types.
Relay outputs 230 V AC
Transistor outputs 24 V DC/50 mA
Controller type
Cooling
Alarm
81, 82, 83
91, 92, 93
UA 410 L
Positive
Inverted
Without function
Without function
Mode of operation „positive"
means that operation of the relay is not inverted:The relay is energized
when the controller activates the function output (e.g. cooling = ON).(This means that the contact of a
normally open relay is closed.)The relay is not energized when the controller deactivates the function
output (e.g. cooling = OFF). (This means that the contact of a normally open relay is open.)
Mode of operation „inverted"
means that operation of the relay is inverted:The relay is not energized
when the controller activates the function output (e.g. alarm = ON). (This means that the contact of a
normally open relay is open.)The relay is energized when the controller deactivates the function output
(e.g. alarm = OFF).(This means that the contact of a normally open relay is closed.)
Содержание UA 410 L AC
Страница 7: ...Firmware V3 00 05 08 2019 7 100 ...