6.6 Firmware Update
The case controller is supplied with the current firmware, ready for operation. Future software versions can be
loaded into the case controller as required by means of a firmware update, and thus updated
.
A software update must only be performed by trained personnel is only to be carried out by trained
personnel or at the factory by the manufacturer. Further details about the current firmware can be
found in
.
Damage to the installation and stock loss! Before
the firmware update, the affected system
component and the system must be brought into a safe state as the shutdown of the controller during
the firmware update can have undesired effects on the system component and/or the
system.
Caution: data loss!
The loading of software via firmware update must not be interrupted. The
power cable and USB A-B cable must not be disconnected during the firmware update. It must be
ensured that power is supplied throughout the entire process. Any interruption of the firmware update
can result in an inoperative controller. In some cases, a change of firmware version can result in the
loss of all the adjusted setpoints in the case controller. As a precaution, the settings
should
therefore
be backed up by saving them using the LDSWin PC software
before
the firmware update. After the
firmware update, the saved settings can be reloaded into the case controller from LDSWin.