Firmware V3.00
05.08.2019
53/100
6.6.2.2 Update for controller with 8-pole DIP switch
Controller characteristic: 8-pole DIP switch
The settings depend on the controller type!
Step 1: Set DIP switch S3 and connect controller to PC
Before
starting the firmware update, all coding switches 1..8 of the DIP switch S3
must
be set to
ON
:
Connect the controller to the PC via a USB A-B cable while
disconnected from the power supply
:
Then supply the controller with power again, see chapter
Terminal assignment for 230 V AC power supply
The steps described in the chapter
Voraussetzungen für das Firmware-Update
performed once for each PC in order to perform a successful firmware update.
Practical tip:
The original position of the coding switches 1..8 of the DIP switch S3 should be
documented, e.g. with a mobile telephone photo.
After
the firmware update has been performed, the coding switch 9 of DIP switch S3 must be
reset to
its original position
.