Firmware V3.00
05.08.2019
19/100
5.2 Selection of the temperature sensors
The case/coldroom controller uses two-wire NTC temperature sensors to perform control.
All sensors connected must be the same type and parameters are not set separately for the sensors. The
type of sensor used can be defined by the Sensor Type parameter (Menu 6-2-5).
The following NTC sensor types are usable:
• L243 (K243) Temperature range -50°C to 50°C;
Type K243 sensor can be used in place of type L243. Characteristics of these two sensors are identical.
• K277 Temperature range -50 to 50°C
•
5K3A1Temperature range 0 to 100°C
For details of the dimensions see chapter
Mechanical data of the temperature sensor L243 / 5K3A1
Detailed information on the temperature sensors is contained in the data sheet
temperature sensor L243 / 5K3A1
All due care must be exercised when installing temperature sensors. Sensor leads need not be
shielded when installed exclusively within the refrigerated display case to be controlled and when
interference is not to be expected (for example from power wires running parallel to the leads.
Otherwise suitable precautions must be taken to protect the sensor leads from external interference.
Содержание UA 410 L AC
Страница 7: ...Firmware V3 00 05 08 2019 7 100 ...