Function of CI 3000
19
Version 2.09 09. April 2014
Procedure
with example:
1. Specify the alarm destinations
The refrigeration plant is to register with the service centre and the building control technology by the caretaker.
2. Specify the priorities and priority groups and assign them to the alarm destinations
Refrigeration plant:
Priorities 0..9
Entire building control technology:
Priorities 10..99
3. Set the priorities in the components accordingly
(the meaning of the priorities X1 and X2 in combination
with the alarm relay is to be observed, see chapter 4.1.2.1)
Components/controllers of the refrigeration plant send messages with the priorities 0..9
Building control equipment components (heating, air conditioning,..) with the priorities 10..99
The settings are to be planned and entered with care. In the event of a false configuration there is
potential for alarms to be sent to the wrong alarm destinations and not given the necessary attention.
In order to illustrate the priority concept and the decades (priority groups) they are listed in the following table
and explained using examples:
Vertical
Maintenance-group-dependent alloca
tion of alarm priorities X0..X9 in deca
des (priority groups)
Refrig.
system
Heating
Air
condit-
ioning
...
...
Horizontal
Logical classification of alarms and messages according to alarm No.
The alarm priorities listed to the left are
1 *
2 *
1
1
1
2
2
1
2
2
...
9
1
9
2
- interpreted as an alarm
- entered into the alarm and the message list
- generate remote alarm messages via modem in accordance with the configuration
- generate local alarms via horn and buzzer (store computer and operator terminal)
- are coupled to the two alarm relays and LEDs ”PRIO1”, i.e. ”PRIO2”
3
...
8
1
3
...
1
8
2
3
...
2
8
...
9
3
...
9
8
- interpreted as an alarm
- entered into the alarm and the message list
- generate remote alarm messages via modem in accordance with the configuration
- generate local alarms via horn and buzzer (store computer and operator terminal)
- depending on the configuration the AUX relay is activated
9
1
9
2
9
...
9
9
- only interpreted as a locally relevant alarm (e.g. open NT coldroom door)
- entered into the alarm and message list
- generate local alarms via horn and buzzer (store computer and operator terminal)
- depending on the configuration the AUX relay is activated
- no remote alarm messaging via modem
0 *
1
0
2
0
...
9
0
- interpreted as message
- entered into the message list
- no alarm signal generated (no signal tone, buzzer)
*: Alarm priorities of a store computer with a firmware version <5.0
Содержание CI 3000
Страница 20: ...Application of CI 3000 14 Version 2 09 09 April 2014 Notice ...
Страница 62: ...Installation and Startup of CI 3000 SIOX 56 Version 2 09 09 April 2014 Notice ...
Страница 118: ...Menu structure of CI 3000 112 Version 2 09 09 April 2014 Notice ...
Страница 120: ...Decommissioning and disposal 114 Version 2 09 09 April 2014 Notice ...
Страница 126: ...Alarms and Messages of CI 3000 120 Version 2 09 09 April 2014 Notice ...