Installation and Startup of CI 3000 / SIOX
41
Version 2.09 09. April 2014
5.5.3
SIOX - Connecting to energy, gas and water meters
Only meters having a S0 interface are supported (reed contact or 24 V DC transistor output). Compared to reed
contact meters, polarity needs to be observed when connected transistor-output meters. The SIOX Extension
Module provides 24 V DC at terminals 93 (-) and 94 (+) for power supply to the S0 interface:
The digital inputs required for this purpose must be configured by jumpers as 24 V AC inputs (see
Section 4.3.1).
Warning - hazardous electrical voltage!
Danger external voltage!
Jumpers must always be configured while disconnected from power and
with connectors removed from inputs (terminals A1, A2 / to / L1, L2), because these terminals may
carry 230 V AC power!
Praxis TIP
What can be done in the event of chattering relay contacts:
Relay contacts have the disadvantage that
they can chatter as a consequence of their mechanical construction. When activated a force is applied to the
contact which enables it to open and close, covering a distance in the micro-millimetre range.
Consequence:
Repeated impulses at the S0 input, which generally results in excessive values at the electri
city meter!
Diagnosis options:
Reading off the impulses in menu 6-2 - the incoming impulses are displayed 3 times to
the right: If the impulses count e.g. 10, 12, 14, 15, 17.... then this is an indication of chattering contacts.
Remedy:
With the parameter „Delay“ under menu 6-1-1 it is possible to increase the delay time for the con
tact’s’ pulse edges.
Configuring meter and transformer constant (Menu 6-1-6-1):
1. Meter constant
(pulses per kWh or m
3
)
2. Unit
(kWh or m
3
)
2. Transformer constant
(conversion ratio of current transformer)
Allowance must be made for the meter and transformer constant settings when using electronic me
ters, as otherwise energy evaluation by the CI 3000 Store Computer will be inaccurate due to faulty
meter and transformer ratios!
Содержание CI 3000
Страница 20: ...Application of CI 3000 14 Version 2 09 09 April 2014 Notice ...
Страница 62: ...Installation and Startup of CI 3000 SIOX 56 Version 2 09 09 April 2014 Notice ...
Страница 118: ...Menu structure of CI 3000 112 Version 2 09 09 April 2014 Notice ...
Страница 120: ...Decommissioning and disposal 114 Version 2 09 09 April 2014 Notice ...
Страница 126: ...Alarms and Messages of CI 3000 120 Version 2 09 09 April 2014 Notice ...