Pin and Terminal Assignments of CI 3000 / SIOX
62
Version 2.09 09. April 2014
6.2.1
SIOX - Terminal assignment of digital inputs 24 V AC/DC / 230 V AC
The 12 digital inputs (24 V AC / 230 V AC) are designed for installation monitoring and as meter inputs.
Warning - hazardous electrical voltage!
Danger of electric shock!
Jumpers
must always
be configured while disconnected from power
and with connectors removed from inputs (terminals A1, A2 / .. / L1, L2), because these terminals
may carry 230 V AC power! The SIOX Extension Module will be destroyed if 230 V AC power is ap
plied to an input configured for 24 V AC!
Wiring of digital inputs:
230 V AC:
The N conductors
must
be connected on one terminal level (A2 .. L2)!
24 V AC/DC:
If 230 V AC
and
24 V AC/DC inputs are required on a SIOX module
they
must
be seperated by one input which must be connected to PE!
For further details see chapter 5.5.2!
Note:
In the following example the first 3 digital inputs (inputs A / B / C - 230 V AC) of the SIOX extension mo
dule are used for installation monitoring and the last input (L - 24 V AC) is used for an electricity meter.
Terminal No.
Input
Function
Without switches
With switches
A1, A2
50, 51
1
Message, alarm, meter, high tarif/low tarif, sync inputs
B1, B2
52, 53
2
C1, C2
54, 55
3
D1, D2
56, 57
4
E1, E2
58, 59
5
F1, F2
60, 61
6
G1, G2
62, 63
7
H1, H2
64, 65
8
I1, I2
66, 67
9
J1, J2
68, 69
10
K1, K2
70, 71
11
L1, L2
72, 73
12
Содержание CI 3000
Страница 20: ...Application of CI 3000 14 Version 2 09 09 April 2014 Notice ...
Страница 62: ...Installation and Startup of CI 3000 SIOX 56 Version 2 09 09 April 2014 Notice ...
Страница 118: ...Menu structure of CI 3000 112 Version 2 09 09 April 2014 Notice ...
Страница 120: ...Decommissioning and disposal 114 Version 2 09 09 April 2014 Notice ...
Страница 126: ...Alarms and Messages of CI 3000 120 Version 2 09 09 April 2014 Notice ...