Application of CI 3000
13
Version 2.09 09. April 2014
3
Application of CI 3000
S
Centralized parameter setting and configuration
of all LDS components via CAN bus:
The CI 3000 Store Computer can be used for remote control and configuring of all LDS components from a sin
gle location via CAN bus. In-use change of the user language can also be made from the central location.
S
The CI 3000 Store Computer's RS232 interface (COM2) with the RS232/RS485 Converter can be used to in
tegrate UA 30 Rx compact controllers / Dixell controllers as well as external controllers into the LDS system.
S
CI 3100 only: UA 30 Rx compact controllers and Dixell controllers can be directly integrated in the LDS system
via the RS485 interface (COM3). The RS232 interface (COM2) is then available for the integration of external
controllers or as a BMS data interface to external systems.
S
Centralized display of operating data, messages and alarms generated by all LDS components.
S
Alarm signalling by indicator light and buzzer and by external horn and alarm contacts.
S
Monitoring of two connected external digital signals (external alarms and meter)
S
Monitoring of CAN bus and operational status of all LDS components:
Alarm is generated in fault or failure of CAN bus and failure of LDS components.
S
Centralized time synchronization (master clock):
Date and time can be set with the CI 3000 Store Computer for the complete system. The CI 3000 Store Com
puter also performs cyclic synchronization of internal clocks in all LDS components via the CAN bus. The
CI 3000 contains a battery-backed real-time clock, which supports automatic daylight saving change.
S
Remote maintenance of the installation / store via a central computer (PC) with the PC software LDSWin.
S
Energy management:
Power, water, gas meters and heat meters with a pulse output (S0) can be connected to the CI 3000
Store Computer i.e. also the M-bus meter by means of the M-bus gateway, which then determines and
archives current power or flow rate and the daily energy requirement or consumption.
S
Load Shedding Manager (LSM)
Load Shedding Manager can be configured for up to 20 shedding points and optimizes power input of the re
frigeration/building control system within a load optimizing interval of 15 min.
S
Remote alarming of LDS System Alarm signal transmitted to fault indicator centre
via modem, GSM, SMS, FAX, voice message and network.
Содержание CI 3000
Страница 20: ...Application of CI 3000 14 Version 2 09 09 April 2014 Notice ...
Страница 62: ...Installation and Startup of CI 3000 SIOX 56 Version 2 09 09 April 2014 Notice ...
Страница 118: ...Menu structure of CI 3000 112 Version 2 09 09 April 2014 Notice ...
Страница 120: ...Decommissioning and disposal 114 Version 2 09 09 April 2014 Notice ...
Страница 126: ...Alarms and Messages of CI 3000 120 Version 2 09 09 April 2014 Notice ...