11
Default Settings for ERDRC
Repeater
Disabled
Status
Disabled
Dimming Output
Enabled
Time-Outs
Motion Sensor
15 Minutes
Switch
No Time Out
Auto-ON
Enabled with no linked switch, disabled with linked wall switch
Light-ON-Setpoint
60% of Sensor FSR
Light-OFF-Setpoint
85% of Light-ON Setpoint
Max Dimming Level 100%
Min Dimming Level 0%
Status Feedback Telegram
EEP:A5-11-01
DB_3 Illumination
0 … 510lx, linear n=0…255
DB_2 Illumination Set Point
Min. … Max., linear n=0…255
DB_1: Dimming Output
Level Min. … Max., linear n=0…255
DB_0.BIT_7: Repeater
0b0 disabled, 0b1 enabled
DB_0.BIT_6: Power Relay Timer
0b0 disabled 0b1 enabled
DB_0.BIT_5: Daylight Harvesting
0b0 disabled 0b1 enabled
DB_0.BIT_4: Dimming
0b0 switching load 0b1 dimming load
DB_0.BIT_3: Learn button
0b0 Teach-in telegram 0b1 Data telegram
DB_0.BIT_2: Magnet Contact
0b0 open 0b1 closed
DB_0.BIT_1: Occupancy
0b0 unoccupied 0b1 occupied
DB_0.BIT_0: Power Relay
0b0 off 0b1 on