15

When the dimming output is enabled, the value selected becomes the maximum 

dimming set point. With the dimming output disabled, the value becomes the 

Light-ON-Set point.

Control Response with Dimming Output Enabled

In the diagram, the red (thick) line indicates the dimming output. The output 

will begin lowering as the light level increases. The point where the light output 

begins dimming down is the maximum dimming set point. The minimum 

dimming set point is 20% greater than this value.

Control Response with Dimming Output Disabled

•  Enter Smart Click configuration mode and click the switch ON or OFF until 

the light is blinking eight times.

•  Press ON for 3 seconds. Default setting is 60% of the light sensors full 

range. If the dimming output is enabled, there are 10 steps from 10% to 

100% the light will blink the step count. If the dimming output is disabled, 

then there 5 steps, 20% to 100% 

in 20% increments.

•  Click on to increase the set-point, 

off to decrease the set-point.

•  To continue with configuration, 

press ON for 3 seconds, the light 

will resume blinking eight times. 

To exit Smart Click press OFF for 5 

seconds.

• 

Maximum Dimming Output Level

 

sets the maximum level of the 

dimming output.

•  Enter Smart Click configuration 

mode and click the switch ON or 

OFF until the light is blinking  

nine times.

Light Blinks

Lighting Set point

1 Blink

10%

2 Blinks

20%

3 Blinks

30%

4 Blinks

40%

5 Blinks

50%

6 Blinks

60% – Default

7 Blinks

70%

8 Blinks

80%

9 Blinks

90%

10 Blinks

100%

Содержание ERDRC-EC

Страница 1: ...l backs and installation expense Using just a wireless wall switch the facility maintenance engineer can adjust setting on the installed controllers eliminating a service call to an electrician This g...

Страница 2: ...d while the light s are on and the timer is counting down an additional period of time is added to the timer total For example if the timer setting is 1 hour and the user pressed the switch ON twice t...

Страница 3: ...ights turn off There are 6 settings for this time out period The time out period is 15 minutes by default but can be set to a value of 5 to 25 minutes in 5 minute increments see the configuration sect...

Страница 4: ...draw 100 feet 30m diameter circles to identify optimal transmitter and controller locations Refer to the table for range considerations with other building materials Material Attenuation Material Ran...

Страница 5: ...o go around the obstacle Do not locate receivers close to other high frequency transmitters Leave at least 2 between the receiver and any other source of interference including lighting ballasts compu...

Страница 6: ...hes remotely Using the ERDRC with a wired wall switch If the circuit will have an additional hard wired switch wire the ERDRC in series before the switch Wiring Instructions Power to the controller is...

Страница 7: ...ill remain lit for 4 seconds while it links the new device It will resume toggling allowing you to link another device up to a total of 20 devices Linking a switch or sensor that is already linked to...

Страница 8: ...controllers relay off lights off to ignore the Simple Tap changes Simple Tap allows you to Enable or disable the motion sensor Auto ON feature Set the motion sensor Auto OFF timer Set the Light ON OFF...

Страница 9: ...ff until the light level decreases to the minimum dimming set point where the relay will close lights ON and the dimming output will increase as the natural light decreases Control Response with Dimmi...

Страница 10: ...bled the absolute value selected becomes the maximum dimming set point If the output is disabled the absolute value selected becomes the Light ON Set point With the light on tap the light sensors teac...

Страница 11: ...P A5 11 01 DB_3 Illumination 0 510lx linear n 0 255 DB_2 Illumination Set Point Min Max linear n 0 255 DB_1 Dimming Output Level Min Max linear n 0 255 DB_0 BIT_7 Repeater 0b0 disabled 0b1 enabled DB_...

Страница 12: ...ure the controller parameters Entering Smart Click Configuration Mode It is important to have feedback light from the ERDRC controller during configuration Using a linked switch see above turn the lig...

Страница 13: ...me blinking three times To exit Smart Click press OFF for 5 seconds Status Telegram the ERDRC can broadcast a status telegram per EEP A5 11 01 The telegram will broadcast every 100 seconds Refer to th...

Страница 14: ...figuration mode and click the switch ON or OFF until the light is blinking six times Press ON for 3 seconds If the auto on function is enabled the light will turn ON if disabled the light will be OFF...

Страница 15: ...ng eight times Press ON for 3 seconds Default setting is 60 of the light sensors full range If the dimming output is enabled there are 10 steps from 10 to 100 the light will blink the step count If th...

Страница 16: ...nking ten times This concludes the configuration directions for the ERDRC controller Echoflex Solutions Inc 1 38924 Queens Way Squamish BC Canada V8B 0K8 Toll Free 888 324 6359 Phone 778 733 0111 Fax...

Отзывы: