CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL
30 / 106
0
– complex function, the initiation of which configures the parameters listed below
as another set of parameters;
1
– type of zone response (DEC type parameter):
o
0 – instant
o
1 – delay
o
2 – 24h burglary
o
3 – arming/disarming
o
4 – 24h tamper
o
5 – interior delayed
o
6 – 24h burglary silent
o
7 – 24h fire
2
– delay in seconds for the circuit of selected “delay” response type (DEC type
parameter). For other response types the parameter is irrelevant.
3
– operation mode (DEC type parameter):
o
0 – unused circuit
o
1 – NC mode
o
2 – NO mode
o
3 – EOL/NC mode
o
4 – EOL/NO mode
o
5 – DEOL/NC mode
o
6 – DEOL/NO mode
4
– number of alarms after which the zone will be automatically blocked until re-
arming (DEC type parameter). If 0, zone will not be blocked.
5
– zone options (BIT type parameter):
o
1 – circuit ignored during arming – i.e. can be violated during partition arming
(e.g. delay circuits shall be set to that option).
o
2 – generates alarm when violated after arming
6
– sensitivity in milliseconds, i.e. after what time the input is considered to change
its status – default value; 400ms
Example:
a)
change of a single parameter – operation mode of number 2 zone into NO
operation mode:
b)
change of sensitivity of all zones into 200 milliseconds:
c)
change of many parameters at the time for zone 1 using complex functions – zone
1 is to be set as immediate circuit, in NC mode, to be blocked after 8 violations
and generate alarm when violated after arming, with the 500ms sensitivity:
… …