CPX200N ALARM CONTROL UNIT – INSTALLER MANUAL
32 / 106
b)
change of 3 output type into triggered by power failure:
c)
change of many parameters at the time for output 1 using complex function –
output 1 is to be set as alarm signalling with activation time 120 seconds:
Note:
In case of complex function (programming many
parameters at the time) after the parameter is entered and confirmed
with
the parameter is saved in the configuration memory and the
system waits for entering another parameter, and so on, until all
parameters of the complex service function are entered. Press
to
cancel changes entered in currently configured parameter only and
exit service function – previously entered parameters, confirmed with
,
will not be cancelled.
6.10.
PARTITION CONFIGURATION
Partition configuration can be configured similarly as zones and outputs, using complex
service functions after activation of which, all the parameters related to the relevant
partition can be given subsequently or in a form of series of service functions that configure
one partition-related parameter. Addresses of partition configuration functions are defined
as per the following pattern:
<XX> <Y>
where:
XX
– determines the number of partition from
01
to
02
; entering number
00
will change
the parameters for both partitions,
Y
– number of parameter related to a selected partition:
0
– complex function, the initiation of which configures the parameters listed below
as another set of parameters;
1
– zones belonging to partition (BIT type parameter),
2
– outputs belonging to partition (BIT type parameter),
3
– time for leaving the partition in seconds (DEC type parameter),
4
– alarm time in the partition in seconds (DEC type parameter),
5
– partition options (BIT type parameter):
o
1 – quiet signalling of time for entering (during counting the time for entering, the
buzzer in a keypad is not active)
o
2 – quiet signalling of time for leaving (during counting the time for leaving, the
buzzer in a keypad is not active)
6
– auto-arming time (DEC type parameter, time of day written in the 24-hour
notation in the form HHMM),
7
– auto-arming option (BIT type parameter):