Do not touch the air inlet or the aluminum fins of the unit.
•
Do not operate the unit if it is dropped, damaged or showing signs of product malfunction.
•
Do not clean the appliance with any chemicals.
•
Ensure the unit is far away from fire, inflammable, or explosive objects.
•
The unit shall be installed in accordance with national wiring regulations.
•
Do not use means to accelerate the defrosting process or to clean, other than those
recommended by the manufacture.
•
The appliance shall be stored in a room without continuously operation sources (for example:
open flames, an operating gas appliance or an operating electric heater).
•
The appliance shall be stored so as to prevent mechanical damage from occurring.
•
Do not piece or burn, even after use.
•
Be aware that refrigerants may not contain an odour.
•
Pipe-work shall be protected from physical damage and shall not be installed in an unventilated
space, if that space is smaller than 9m².
•
Compliance with national gas regulations shall be observed.
•
Keep any required ventilation openings clear of obstruction.
•
The appliance shall be stored in a well-ventilated area where the room size corresponds to the
room area as specified for operation.
Any person who is involved with working on or breaking into a refrigerant circuit should
hold a current valid certificate from an industry-accredited assessment authority, which
authorizes their competence to handle refrigerants safely in accordance with an industry,
recognized assessment specification.
Servicing shall only be performed as recommended by the equipment manufacturer.
Maintenance and repair requiring the assistance of other skilled personnel shall be carried
out under the supervision of the person competent in the use of flammable refrigerants.
If you don’t understand something or need help, please contact the dealer services.
Please follow these warnings when to undertake the following when servicing an appliance with R290.
1. INFORMATION ON SERVICING
1.1. Checks to the area
Prior to beginning work on systems containing flammable refrigerants, safety checks are necessary
to ensure that the risk of ignition is minimised. For repair to the refrigerating system, the following
precautions shall be complied with prior to conducting work on the system.
1.2. Work procedure
Work shall be undertaken under a controlled procedure so as to minimise the risk of a flammable gas or
vapour being present while the work is being performed.
1.3. General work area
All maintenance staff and others working in the local area shall be instructed on the nature of work being
carried out. Work in confined spaces shall be avoided. The area around the workspace shall be sectioned
off. Ensure that the conditions within the area have been made safe by control of flammable material.
1.4. Checking for presence of refrigerant
The area shall be checked with an appropriate refrigerant detector prior to and during work, to ensure
the technician is aware of potentially flammable atmospheres. Ensure that the leak detection equipment
being used is suitable for use with flammable refrigerants, i.e. non-sparking, adequately sealed or
2.2. Precautions during maintenance and servicing of the unit filled with R290
WARNING
WARNING