12 Sample project
12.8 Finding XN300 slice module PDOs and SDOs
96
XN-312-GW-EC gateway
07/20 MN050010-EN Eaton.com
12.8.3 XN-322-4AI-PTNI
SDO start parameters for XN-322-4AI-PTNI
The SDOs can be shown under the XN_322_4AI_PTNI/Start parameters tab.
Figure 64:
XN-322-4AI-PTNI start parameters
PDO process data for XN-322-4AI-PTNI
The PDOs can be shown under the XN_322_4AI_PTNI/Module I/O image
table tab.
Figure 65:
XN-322-4AI-PTNI module input/output parameters
The XN300 slice module's process data is also stored in the XN-312-GW-EC
gateway process data. The analog inputs are stored in the 0x6xxx
object
range. The ModuleID in the sample project is 2, and the inputs are accord-
ingly stored in object 0x6021. The module does not have any outputs.
The description of the objects for the analog inputs; please refer to