2 XN-312-GW-EC gateway
2.7 LED status indicators
20
XN-312-GW-EC gateway
07/20 MN050010-EN Eaton.com
RN (EtherCAT Run)
green
Continuous light
OPERATIONAL
Fast flashing
INITIALIZATION or BOOTSTRAP
Single flash
SAFE OPERATIONAL
Fast flickering
PRE-OPERATIONAL
AUS
–
INIT
ER (EtherCAT Error)
red
Continuous light
PDI watchdog timeout
The field bus has been turned off due to an error,
e.g.,
• Wiring faults
• Module with wrong baud rate on bus
Fast flashing
Boot error
Double flash
Watchdog timeout
Single flash
General runtime error
Fast flickering
Configuration not OK
AUS
–
No errors or faults
IN (EtherCAT)
yellow
Continuous light
Connection to upstream EtherCAT node estab-
lished
Flashing
Data communication with upstream EtherCAT
node established
AUS
–
No connection to upstream EtherCAT node
OUT (EtherCAT)
yellow
yellow
Continuous light
Connection to downstream EtherCAT node
established
Flashing
Data communication with downstream
EtherCAT node established
AUS
–
No connection to downstream EtherCAT node
X3 (DC power OK)
green
Continuous light
+24 VDC power OK
AUS
–
+24 VDC power faulty
LED
Color
EtherCAT status
Description
Содержание XN-312-GW-EC
Страница 1: ...Manual EtherCAT gateway XN 312 GW EC 07 20 MN050010 EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Writing conventions 8 XN 312 GW EC gateway 07 20 MN050010 EN Eaton com...
Страница 68: ...10 XN300 Assist 10 1 Firmware update with XN300 Assist 64 XN 312 GW EC gateway 07 20 MN050010 EN Eaton com...
Страница 95: ...12 Sample project 12 7 What will be transferred XN 312 GW EC gateway 07 20 MN050010 EN Eaton com 91...
Страница 102: ...12 Sample project 12 8 Finding XN300 slice module PDOs and SDOs 98 XN 312 GW EC gateway 07 20 MN050010 EN Eaton com...
Страница 130: ...126 XN 312 GW EC gateway 07 20 MN050010 EN Eaton com...