8 Installation
8.1 Mounting
50
XN-312-GW-EC gateway
07/20 MN050010-EN Eaton.com
8.1 Mounting
8.1.1 Installation prerequisites
Install the XN-312-GW-EC gateway in a control panel, a distribution board or
an enclosure so that the power supply and terminal capacities cannot be
touched accidentally during operation. Snap the device onto an IEC/EN
60715 DIN-rail.
The DIN-rail must establish a conductive connection to the control panel's
back plate. The device must be installed in a horizontal position (device desig-
nation on top).
In order to ensure that the maximum operating ambient temperature will not
be exceeded, make sure that there is enough clearance between the system
block's vents and any neighboring components, as well as between the
vents and the control panel's back plate.
Figure 16:
Horizontal installation only!
8.1.2 Mounting the system block on the DIN-rail
To mount the system on the DIN-rail, join the XN 300 slice modules and the
gateway to form a system block and then snap the entire system block onto
the DIN-rail.
To mount the system block, follow the steps below:
▶
The gateway must be the first element on the left in the system block.
a
b
c
ϑ
30 mm
(1.18“)
30 mm
(1.18“)
100 mm
(3.94“)
≦
55 °C
(
≦
131 °F)
a
a
b
b
c
Содержание XN-312-GW-EC
Страница 1: ...Manual EtherCAT gateway XN 312 GW EC 07 20 MN050010 EN...
Страница 4: ...II...
Страница 12: ...0 About this manual 0 5 Writing conventions 8 XN 312 GW EC gateway 07 20 MN050010 EN Eaton com...
Страница 68: ...10 XN300 Assist 10 1 Firmware update with XN300 Assist 64 XN 312 GW EC gateway 07 20 MN050010 EN Eaton com...
Страница 95: ...12 Sample project 12 7 What will be transferred XN 312 GW EC gateway 07 20 MN050010 EN Eaton com 91...
Страница 102: ...12 Sample project 12 8 Finding XN300 slice module PDOs and SDOs 98 XN 312 GW EC gateway 07 20 MN050010 EN Eaton com...
Страница 130: ...126 XN 312 GW EC gateway 07 20 MN050010 EN Eaton com...