Instruction Manual for the Eaton RTC-50

Automatic Transfer Switch Controller

2.7 Specification Summary
Table 1. RTC-50 Controller Specifications

SECTION 3:  OPERATION

3.1  General

This section specifically describes the operation and functional use 

of the RTC-50 controller.  The practical use of and operation 

within each category will be discussed.  In this section, it is 

assumed that prior sections of this manual were reviewed and 

that the operator has a basic understanding of the hardware.
The RTC-50 controller provides for automatic transfer and re-

transfer from source to source.  It provides a summary of the 

RTC-50 controller intelligence and supervisory circuits that con-

stantly monitor the condition of both the Utility and Generator 

power sources, thus providing the required intelligence for transfer 

operations.  These circuits, for example, automatically initiate an 

immediate transfer of power when the power fails or the voltage 

level drops below a preset value and an alternate source of power 

is available.  

3.2  Operating Voltage and Measurements

The RTC-50 controller operates on an input voltage of 240 Vac 

with selectable frequency settings of 50 or 60 Hz.
The RTC-50 controller operates directly from the line sensing 

inputs of the Utility and Generator power sources.  
All voltage monitoring and measurements are true RMS measure-

ments.

3.3  Typical Transfer Operation

A typical transfer request will begin with a Utility outage (Utility 

voltage falls below the 70% dropout level).  
When the Generator source meets the requirements to be consid-

ered available, the TDNE (Time Delay Normal to Emergency) timer 

will start timing.  TDNE is jumper-programmable at either 20 sec-

onds or 50 seconds.  The 50 second setting may be used to allow 

for a longer warm-up period of the Generator.  After TDNE times 

out, the Utility Close Outputs will open, the Gen Close Outputs 

will close, and the Load Shed Contacts will open.  This will con-

nect the load to the Generator source but any loads wired to the 

Load Shed Contacts will be disconnected.
When the Utility becomes available (Utility voltage is above the 

80% pickup level), the TDEN (Time Delay Emergency to Normal) 

timer will start timing.  TDEN is a fixed delay of 10 seconds.  After 

TDEN times out, the Gen Close Outputs will open, the Utility 

Close Outputs will close, and the Load Shed Contacts will be 

closed.  This will connect all loads to the Utility source. 

INPUT VOLTAGE

240 VAC

50/60 HZ

Voltage Measurements of

Utility

Generator

Voltage Measurement Range

0 to 300 Vac RMS (50/60 Hz)

Voltage Measurement Accuracy

± 6 Vac

Undervoltage Dropout 

70% of the Nominal 240 Vac Input Voltage

Undervoltage Pickup

80% of the Nominal 240 Vac Input Voltage

Operating Temperature Range

-20 to +70°C (-4 to +158°F)

Storage Temperature Range

-30 to +85°C (-22 to +185°F)

Operating Humidity

0 to 95% Relative Humidity (Non-condensing)

Operating Environment

Resistant to Ammonia, Methane, Nitrogen, Hydrogen, 

and Hydrocarbons

Utility Close and Gen Close Outputs

5 amps @ 250 Vac

5 amps @ 30 Vdc

Load Shed Contacts #1 and #2

5 amps @ 250 Vac

5 amps @ 30 Vdc

Applicable Testing 

UL Recognized Component

UL 1008, UL 991 Environmental

IEC 61000-4-2, 61000-4-3, 61000-4-4, 61000-4-5, 

61000-4-6, 61000-4-11

CISPR 11, Class B

FCC Part 15, Class B

Содержание RTC-50

Страница 1: ...tion Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Instructional Booklet New Information Description Page 1 Introduction 2 2 Hardware Description 4 3 Operation 6 4 Programming 7 5 T...

Страница 2: ...y trans fers back to the Utility and the Generator will shut down after a time delay ATSs automatically perform the transfer function and include three basic elements 1 Main contacts to connect and di...

Страница 3: ...connection 1 5 Functions Features The primary function of RTC 50 controller is to accurately monitor the Utility and Generator power sources and provide the necessary intelligence to operate the ATS i...

Страница 4: ...arize the reader with the RTC 50 controller hardware its nomenclature and to list the unit s specifications 2 2 LED Indicators Utility Available The green Utility Available LED illuminates if the util...

Страница 5: ...tor light to indicate that routine maintenance is required for every 25 hours that the generator has run This will constitute one maintenance cycle The RTC 50 will keep track of the number of hours th...

Страница 6: ...e falls below the 70 dropout level When the Generator source meets the requirements to be consid ered available the TDNE Time Delay Normal to Emergency timer will start timing TDNE is jumper programma...

Страница 7: ...equency of either 50 or 60 hertz Figure 2 RTC 50 Programming Jumpers Table 2 is a summary of the Fixed and Jumper selectable settings that are available in the RTC 50 Table 2 Fixed and Jumper Selectab...

Страница 8: ...Step 3 Disconnect the wires connected to J7 and J8 Step 4 Remove the four 4 screws located at the corners of the controller that secure it to the power panel Remove the controller Step 5 Align the ne...

Страница 9: ...ility is available Is Generator available N ATS connects to Utility Utility Close Output closes TDNE timer times out 20 sec or 50 sec Transfer to Generator Gen Close Output closes Y Generator is power...

Страница 10: ...For more information visit www eaton com IB00405004E 70 8664 Instructional Booklet Page 10 Effective June 2007 Instruction Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Notes...

Страница 11: ...IB00405004E 70 8664 For more information visit www eaton com Instructional Booklet Effective June 2007 Page 11 Instruction Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Notes...

Страница 12: ...between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WAR RANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MER CHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE...

Страница 13: ...para el con trolador RTC 50 del interruptor de transferencia autom tica Eaton Folleto instructivo Nueva informaci n Descripci n P gina 1 Introducci n 2 2 Descripci n del equipo 4 3 Operaci n 6 4 Prog...

Страница 14: ...cuando hay dis ponible suficiente voltaje en el mismo Cuando la fuente de energ a del servicio es restaurada el ATS autom ticamente trans fiere nuevamente al servicio y el generador se interrumpe des...

Страница 15: ...carga desde el servicio hacia la fuente de alimentaci n del generador Desconectado Se define desconectado cuando la entrada no est sometida a cortocircuito por un contacto o conexi n externos 1 5 Func...

Страница 16: ...Indicadores con diodos emisores de luz LED Servicio disponible El diodo emisor de luz verde de disponibilidad del servicio se ilu mina si la fuente de alimentaci n del servicio cumple con los requisi...

Страница 17: ...la luz indicadora del ser vicio del generador para indicar que se requiere un mantenimiento de rutina por cada 25 horas de funcionamiento del generador Esto constituir un ciclo de mantenimiento El RTC...

Страница 18: ...cumple con los requisitos para ser considerada disponible el cronometraje del tiempo de demora de normal a emergencia TDNE comenzar a contar El TDNE es programable en 20 50 segundos La selec ci n de...

Страница 19: ...a de 50 60 Hz Figura 2 Puentes para programaci n del RTC 50 La tabla 2 es un resumen de las selecciones fijas y seleccionables con puente que se encuentran disponibles en el RTC 50 Tabla 2 Selecciones...

Страница 20: ...esquinas del controlador que lo aseguran al panel de energ a Quite el controlador Paso 5 Alinee el nuevo controlador con los agujeros de montaje Asegure el nuevo tablero del controlador utilizando la...

Страница 21: ...a salida del servicio cerrado se cierra El TDNE demora del tiempo de normal a emergencia se interrumpe 20 50 segundos Transferencia al generador La salida del generador cerrado se cierra El generador...

Страница 22: ...informaci n visite www eaton com IB00405004E 70 8664 Folleto instructivo P gina 10 Efectivo Junio 2007 Manual de instrucciones para el controlador RTC 50 del interruptor de transferencia autom tica E...

Страница 23: ...E 70 8664 Para mayor informaci n visite www eaton com Folleto instructivo Efectivo Junio 2007 P gina 11 Manual de instrucciones para el controlador RTC 50 del interruptor de transferencia autom tica E...

Страница 24: ...entre el com prador y Eaton NINGUNA GARANT A EXPRESA O IMPL CITA INCLUYENDO GARANT AS DE APTITUD PARA UN PROP SITO EN PARTICU LAR O APTITUD COMERCIAL O GARANT AS QUE SURJAN DEL CURSO DEL TRATO O USO...

Страница 25: ...emploi de la commande RTC 50 pour commutateur de transfert automatique 50 Eaton Livret d instructions Nouveau document Sommaire Page 1 Introduction 2 2 Description du mat riel 4 3 Fonctionnement 6 4 P...

Страница 26: ...e nouveau au r seau de distribution lectrique Un syst me intelligent active le transfert lorsque le courant sect eur est coup ou devient inf rieur une tension pr r gl e Un d marrage de moteur est alor...

Страница 27: ...r des valeurs de r glage pour les sous tensions pour une dur e d pas sant de 0 5 seconde le point d expiration de la dur e de temporisa tion d urgence TDEF Transfert Changement du branchement de la ch...

Страница 28: ...la commande RTC 50 ses pi ces et ses caract ristiques 2 2 Voyants DEL Disponibilit du courant secteur Le voyant DEL vert de courant secteur disponible s illumine lor sque la source de courant secteur...

Страница 29: ...ecte le nombre d heures de fonctionne ment de la g n ratrice Apr s 25 heures de marche elle allume le voyant pour indiquer le besoin d entretien p riodique Ceci con stitue un cycle d entretien La comm...

Страница 30: ...ratrice satisfait aux conditions exig es de disponibilit la temporisation de normal secours TDNE d bute la temporisation est programmable par cavalier 20 ou 50 secondes Le r glage 50 secondes peut tr...

Страница 31: ...TC 50 Le tableau 2 est un r sum des r glages fixes et choisir avec cavaliers dans la commande RTC 50 Tableau 2 R glages fixes et choisir avec cavaliers DESCRIPTION VALEURS VALEUR PAR D FAUT USINE FIXE...

Страница 32: ...fils reli s aux prises J7 et J8 tape 4 D posez les quatre 4 vis situ es aux coins de la com mande pour la fixer sur le panneau lectrique D posez la commande tape 5 Alignez la nouvelle commande sur le...

Страница 33: ...ecteur la sortie de fermeture du courant secteur se ferme Temporisation de normal secours TDNE 20 ou 50 secondes Transfert vers la g n ratrice la sortie de fermeture du courant de g n ratrice se ferme...

Страница 34: ...mples renseignements visitez www eaton com IB00405004E 70 8664 Livret d instructions Page 10 En vigueur d s juin 2007 Mode d emploi de la commande RTC 50 pour commutateur de transfert automatique 50 E...

Страница 35: ...8664 Pour de plus amples renseignements visitez www eaton com Livret d instructions En vigueur d s juin 2007 Page 11 Mode d emploi de la commande RTC 50 pour commutateur de transfert automatique 50 E...

Страница 36: ...LES GARANTIES MANANT DE CONDUITES HABITU ELLES OU D USAGE COMMERCIAL N EST TABLIE PAR RAPPORT AUX INFORMATIONS RECOMMANDATIONS ET DESCRIPTIONS CONTENUES DANS CE DOCUMENT Eaton ne peut en aucun cas tr...

Отзывы: