background image

IB00405004E-70-8664

For more information visit: www.eaton.com

Instructional Booklet

Effective: June 2007

Page

 

5

Instruction Manual for the Eaton RTC-50 

Automatic Transfer Switch Controller

2.5  Go To Generator Input

The RTC-50 has a control input signal that will initiate a transfer 

from Utility to Generator.  The input requires an external contact 

closure to the Go To Generator input (J6, pins 1 and 2).
The Control Input “State” definitions are as follows.

Connected - 

When the input is shorted by an external contact or 

connection.

Unconnected - 

When the input is NOT shorted by an external con-

tact or connection.

The Go To Generator Input operations are defined as follows.
When this input (J6, pins 1 and 2) is in the “Connected” state, the 

RTC-50 will initiate a transfer from Utility to Generator.  The Gen-

erator must be manually started or the Utility sensing wires must 

be interrupted in order to initiate an engine start.  After the Gener-

ator becomes available, TDNE will time out before the transfer to 

Generator takes place.  Re-transfer will occur when the external 

contact is opened or under a failsafe condition. 

2.6  Output Connections

The RTC-50 output connections are divided into two categories:

Customer Connections 

Transfer Operation Connections.

2.6.1 Customer Connections

Load Shed Contacts 

There are two sets of load shed contacts for customer use on con-

nector J7, Load Shed Contacts #1 and Load Shed Contacts #2.  

Both sets of contacts are closed when the transfer switch is in the 

Utility position and both sets are open when the transfer switch is 

in the Generator position.  The output contacts are rated for 5 

amps @ 250 VAC.  The DC rating is 5 amps @ 30 VDC.

Generator Service Indicator Light

The Generator Service Indicator Light is wired to connector J8, 

pins 1 and 2.  A 5mm panel-mount LED with a maximum current 

rating of 25 mA is recommended (Dialight 559-5101-007F or 

equivalent).  The LED can be located up to 1000 feet away from 

the RTC-50.

The LED is polarity sensitive.  The red lead must be wired to J8, 

pin 1 and the black lead must be wired to J8, pin 2.  If the wiring 

is reversed, the LED will not light.
The RTC-50 will track the number of hours that the generator has 

run.  It will then turn on the Generator Service Indicator light to 

indicate that routine maintenance is required for every 25 hours 

that the generator has run.  This will constitute one maintenance 

cycle.
The RTC-50 will keep track of the number of hours that the gener-

ator has run for up to 1000 hours.  At this point, the counter will 

roll over and start again.  The information is stored in non-volatile 

memory so that the value is retained when there is a loss of 

power.
The end-user will press the Gen Service Reset Switch to retrieve 

the generator run time information.  The indicator will flash both 

long and short flashes to indicate the number of hours the genera-

tor has run.   Each long flash (1 second) of the indicator equals 

100 hours of run time and each short flash (0.2 second) equals 25 

hours of run time.

Generator Service Reset Switch

The Generator Service Reset Switch is wired to connector J8, pins 

3 and 4.  A momentary single-pole, single-throw (SPST) pushbut-

ton with normally open (N.O.) contacts is recommended (Judco 

40-4313-00 or equivalent).  The contact rating must be at least 

50 mA at 24 V.  When the pushbutton is pressed, the contacts 

will close across J8, pins 3 and 4.  The pushbutton can be located 

up to 1000 feet away from the RTC-50.

The Generator Service Reset Switch will enable the end-user to 

retrieve information via the Generator Service Indicator Light indi-

cating the number of hours that the generator has run.  The Gen-

erator Service Indicator Light will flash long (1 second) flashes for 

each 100-hour interval and short (0.2 second) flashes for each 25-

hour interval in that order.  The Generator Service Reset Switch 

may be pressed at any time to retrieve the Generator run time 

information to the nearest 25 hours.

For example, a Generator run time of 450 hours would be shown 

as four 100-hour long flashes of 1 second each followed by two 

25-hour short flashes of 0.2 seconds each.

Pressing the Generator Service Reset Switch will also turn off the 

Generator Service Indicator Light if it had been lit.

2.6.2 Transfer Operations Connections

The Utility Close and Gen Close outputs are factory wired to oper-

ate the transfer switch.  The relay contacts for each output are 

rated for 5 amps @ 250 VAC.  The DC rating is 5 amps @ 30 

VDC.

Utility Close Outputs

This output is used to transfer to Utility.  The Utility Close Outputs 

are on J6, pins 5 and 6.

Generator Close Outputs 

This output is used to transfer to Generator.  The Generator Close 

Outputs are on J6, pins 3 and 4.

Содержание RTC-50

Страница 1: ...tion Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Instructional Booklet New Information Description Page 1 Introduction 2 2 Hardware Description 4 3 Operation 6 4 Programming 7 5 T...

Страница 2: ...y trans fers back to the Utility and the Generator will shut down after a time delay ATSs automatically perform the transfer function and include three basic elements 1 Main contacts to connect and di...

Страница 3: ...connection 1 5 Functions Features The primary function of RTC 50 controller is to accurately monitor the Utility and Generator power sources and provide the necessary intelligence to operate the ATS i...

Страница 4: ...arize the reader with the RTC 50 controller hardware its nomenclature and to list the unit s specifications 2 2 LED Indicators Utility Available The green Utility Available LED illuminates if the util...

Страница 5: ...tor light to indicate that routine maintenance is required for every 25 hours that the generator has run This will constitute one maintenance cycle The RTC 50 will keep track of the number of hours th...

Страница 6: ...e falls below the 70 dropout level When the Generator source meets the requirements to be consid ered available the TDNE Time Delay Normal to Emergency timer will start timing TDNE is jumper programma...

Страница 7: ...equency of either 50 or 60 hertz Figure 2 RTC 50 Programming Jumpers Table 2 is a summary of the Fixed and Jumper selectable settings that are available in the RTC 50 Table 2 Fixed and Jumper Selectab...

Страница 8: ...Step 3 Disconnect the wires connected to J7 and J8 Step 4 Remove the four 4 screws located at the corners of the controller that secure it to the power panel Remove the controller Step 5 Align the ne...

Страница 9: ...ility is available Is Generator available N ATS connects to Utility Utility Close Output closes TDNE timer times out 20 sec or 50 sec Transfer to Generator Gen Close Output closes Y Generator is power...

Страница 10: ...For more information visit www eaton com IB00405004E 70 8664 Instructional Booklet Page 10 Effective June 2007 Instruction Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Notes...

Страница 11: ...IB00405004E 70 8664 For more information visit www eaton com Instructional Booklet Effective June 2007 Page 11 Instruction Manual for the Eaton RTC 50 Automatic Transfer Switch Controller Notes...

Страница 12: ...between the purchaser and Eaton NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WAR RANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MER CHANTABILITY OR WARRANTIES ARISING FROM COURSE OF DEALING OR USAGE...

Страница 13: ...para el con trolador RTC 50 del interruptor de transferencia autom tica Eaton Folleto instructivo Nueva informaci n Descripci n P gina 1 Introducci n 2 2 Descripci n del equipo 4 3 Operaci n 6 4 Prog...

Страница 14: ...cuando hay dis ponible suficiente voltaje en el mismo Cuando la fuente de energ a del servicio es restaurada el ATS autom ticamente trans fiere nuevamente al servicio y el generador se interrumpe des...

Страница 15: ...carga desde el servicio hacia la fuente de alimentaci n del generador Desconectado Se define desconectado cuando la entrada no est sometida a cortocircuito por un contacto o conexi n externos 1 5 Func...

Страница 16: ...Indicadores con diodos emisores de luz LED Servicio disponible El diodo emisor de luz verde de disponibilidad del servicio se ilu mina si la fuente de alimentaci n del servicio cumple con los requisi...

Страница 17: ...la luz indicadora del ser vicio del generador para indicar que se requiere un mantenimiento de rutina por cada 25 horas de funcionamiento del generador Esto constituir un ciclo de mantenimiento El RTC...

Страница 18: ...cumple con los requisitos para ser considerada disponible el cronometraje del tiempo de demora de normal a emergencia TDNE comenzar a contar El TDNE es programable en 20 50 segundos La selec ci n de...

Страница 19: ...a de 50 60 Hz Figura 2 Puentes para programaci n del RTC 50 La tabla 2 es un resumen de las selecciones fijas y seleccionables con puente que se encuentran disponibles en el RTC 50 Tabla 2 Selecciones...

Страница 20: ...esquinas del controlador que lo aseguran al panel de energ a Quite el controlador Paso 5 Alinee el nuevo controlador con los agujeros de montaje Asegure el nuevo tablero del controlador utilizando la...

Страница 21: ...a salida del servicio cerrado se cierra El TDNE demora del tiempo de normal a emergencia se interrumpe 20 50 segundos Transferencia al generador La salida del generador cerrado se cierra El generador...

Страница 22: ...informaci n visite www eaton com IB00405004E 70 8664 Folleto instructivo P gina 10 Efectivo Junio 2007 Manual de instrucciones para el controlador RTC 50 del interruptor de transferencia autom tica E...

Страница 23: ...E 70 8664 Para mayor informaci n visite www eaton com Folleto instructivo Efectivo Junio 2007 P gina 11 Manual de instrucciones para el controlador RTC 50 del interruptor de transferencia autom tica E...

Страница 24: ...entre el com prador y Eaton NINGUNA GARANT A EXPRESA O IMPL CITA INCLUYENDO GARANT AS DE APTITUD PARA UN PROP SITO EN PARTICU LAR O APTITUD COMERCIAL O GARANT AS QUE SURJAN DEL CURSO DEL TRATO O USO...

Страница 25: ...emploi de la commande RTC 50 pour commutateur de transfert automatique 50 Eaton Livret d instructions Nouveau document Sommaire Page 1 Introduction 2 2 Description du mat riel 4 3 Fonctionnement 6 4 P...

Страница 26: ...e nouveau au r seau de distribution lectrique Un syst me intelligent active le transfert lorsque le courant sect eur est coup ou devient inf rieur une tension pr r gl e Un d marrage de moteur est alor...

Страница 27: ...r des valeurs de r glage pour les sous tensions pour une dur e d pas sant de 0 5 seconde le point d expiration de la dur e de temporisa tion d urgence TDEF Transfert Changement du branchement de la ch...

Страница 28: ...la commande RTC 50 ses pi ces et ses caract ristiques 2 2 Voyants DEL Disponibilit du courant secteur Le voyant DEL vert de courant secteur disponible s illumine lor sque la source de courant secteur...

Страница 29: ...ecte le nombre d heures de fonctionne ment de la g n ratrice Apr s 25 heures de marche elle allume le voyant pour indiquer le besoin d entretien p riodique Ceci con stitue un cycle d entretien La comm...

Страница 30: ...ratrice satisfait aux conditions exig es de disponibilit la temporisation de normal secours TDNE d bute la temporisation est programmable par cavalier 20 ou 50 secondes Le r glage 50 secondes peut tr...

Страница 31: ...TC 50 Le tableau 2 est un r sum des r glages fixes et choisir avec cavaliers dans la commande RTC 50 Tableau 2 R glages fixes et choisir avec cavaliers DESCRIPTION VALEURS VALEUR PAR D FAUT USINE FIXE...

Страница 32: ...fils reli s aux prises J7 et J8 tape 4 D posez les quatre 4 vis situ es aux coins de la com mande pour la fixer sur le panneau lectrique D posez la commande tape 5 Alignez la nouvelle commande sur le...

Страница 33: ...ecteur la sortie de fermeture du courant secteur se ferme Temporisation de normal secours TDNE 20 ou 50 secondes Transfert vers la g n ratrice la sortie de fermeture du courant de g n ratrice se ferme...

Страница 34: ...mples renseignements visitez www eaton com IB00405004E 70 8664 Livret d instructions Page 10 En vigueur d s juin 2007 Mode d emploi de la commande RTC 50 pour commutateur de transfert automatique 50 E...

Страница 35: ...8664 Pour de plus amples renseignements visitez www eaton com Livret d instructions En vigueur d s juin 2007 Page 11 Mode d emploi de la commande RTC 50 pour commutateur de transfert automatique 50 E...

Страница 36: ...LES GARANTIES MANANT DE CONDUITES HABITU ELLES OU D USAGE COMMERCIAL N EST TABLIE PAR RAPPORT AUX INFORMATIONS RECOMMANDATIONS ET DESCRIPTIONS CONTENUES DANS CE DOCUMENT Eaton ne peut en aucun cas tr...

Отзывы: