109
5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
Group
Parameter
Number
Name
Setting Range
Factory
Value
User
settings
03-02
P.86
DI3 function selection Same as 03-00
30
03-03
P.80
DI4 function selection Same as 03-00
2
03-04
P.81
DI5 function selection Same as 03-00
3
03-05
P.82
DI6 function selection Same as 03-00
4
03-06
P.126
DI7 function selection Same as 03-00
5
03-07
P.127
DI8 function selection Same as 03-00
8
03-08
P.128
DI9 function selection Same as 03-00
7
03-09
P.550
DIH terminal function Same as 03-00
57
03-10
P.40
DO1 - DO-DO1-DO-
function
0: RUN (inverter running)
1
1: SU(reaching the output frequency)
2: FU (output frequency detection)
3: OL (overload detection)
4: OMD (zero current detection)
5: ALARM (alarm detection)
6: PO1 (programmed operation section detection)
7: PO2 (programmed operation periodical detection)
8: PO3 (programmed operation pause detection)
9: BP (Switch between the inverter operation and the com-
mercial power-supply operation function, inverter output)
10: GP (Switch between the inverter operation and the com-
mercial power-supply operation function,commercial
power-supply output)
11: OMD1 (zero current detection)
12~15: Reserve
16: Abnormal signal of fan
17: RY(the accomplishment of inverter running preparation)
18: Maintenance alarm detection
19: OL2 (Over torque alarm output)
20: Capacitor lifetime abnormal
21: Position control position attained
22: Tension control curl pattern detection
23: Power marker detection
03-11
P.85
R1O-R1C-R1MR1O-
R1C-R1M function
Same as 03-10
5
03-12
P.129
DO2 - DO- DO2-DO-
function
Same as 03-10
2
03-13
P.130
R2O-R2C-R2M R2O-
R2C-R2M function
Same as 03-10
0
03-14
P.87
Multi-function termi-
nal digital input nega-
tive/positive logic
0~1023
0
03-15
P.88
Multi-function
terminal digital output
negative/positive
logic (noumenon and
slot 3)
0~4095
0