60
5. Parameter Description
Eaton Electric General Inverters DF1 Series
UMXXXXXXXXE February 2020 www.eaton.com
ote:
N
1. The “output frequency” here is the value after slip compensation.
2. Set the boot screen for the target frequency mode, the “FWD” or “REV” or “STOP” button will cut images for the target
frequency setting mode.
3.The multi-function display selection is realized in the monitoring voltage mode. Please refer to Section 4.2.3 for monitoring
mode selection.
4. Please refer to 5.4.15 for the sort of terminal, 03-59 (P.585) for digital terminal input state, 03-60 (P.586) for digital output
teriminal state.
Display
Parameter unitmonitoring selection
•
Display the current target pressure and feedback pressure of the constant pressure system (00-06=“3”).
At this point, the screen display shows two sections. A decimal point is used to separate the boundaries. What is
on the left is the target pressure of the constant pressure system and what is on the right is the feedback pressure
of the constant pressure system. As is shown in this figure,
0
3
0
2
.
V
A
Hz
PLC
NET
EXT
PU
MON
, 20 denotes that the target pressure of
the constant pressure system is 2.0kg/cm
3
; 30 denotes that the feedback pressure of the constant pressure system
is 3.0kg/cm
3
.
Display
Multi-function display
•
The multi-function display selection is realized in the monitoring voltage mode. Please refer to 4.2.3. The operation
flow charts for monitoring mode with DXF-KEY-LED for for monitoring mode selection.
5.1.5 Speed display
• In the mode of “monitoring output frequency”, the screen displays the corresponding machine speed.
Speed display
•
The setting value of 00-08 is the machine speed of the inverter when its output frequency is 60Hz. For example:
1. If the transmitting belt speed is 950 m/minute when the inverter output frequency is 60Hz, set 00-08 = 950.
2. After setting, in the “output frequency monitoring mode” of parameter unit, the screen will display the speed of
the transmitting belt.
ote:
N
The machine speed on the screen is the theoretical value calculated proportionately by the inverter output frequency and the
setting value of 00-08. So there’s minute discrepancy between the displayed machine speed and the actual one.
Parameter
Name
Factory
Value
Setting Range
Content
00-08
P.37
Speed display
0.0
0
0: Display output frequency(the mechanical speed is not
displayed)
0.1~5000.0
When 00-09=1
1~50000
When 00-09=0
00-09
P.259
Speed unit selection
1
0
0: Speed display selection unit is 1
1
1: Speed display selection unit is 0.1