UPS INSTALLATION PLAN AND UNPACKING
Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual
S
164201725 Rev 4
www.eaton.com/powerquality
3-23
Table 3‐15. Power Cable Conduit Requirements (continued)
Number of
Conduits
Minimum Conduit
Trade Size
Number of Wires
in Conduit
Terminal
Voltage
UPS Model
Eaton 9395-825/825
400 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
5
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
3
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
5
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
5
DC
Battery
(Positive, Negative, Ground)
See Note 1
Eaton 9395-825/450
Eaton 9395-825/500
Eaton 9395-825/550
See Note 2
400 Vac
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
3
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
5
480 Vac
AC Input to UPS Rectifier
(A, B, C, Ground)
4
3
4
AC Input to UPS Rectifier (Separate Feed)
(A, B, C, Ground)
4
2
2
(Each UPM)
AC Input to Bypass and Output (Four Wire)
(A, B, C, Ground)
4
3
4
AC Input to Bypass and Output (Five Wire)
(A, B, C, Neutral, Ground)
5
3
5
DC
Battery
(Positive, Negative, Ground)
See Note 1
NOTE 1
Select conduit taking into consideration the DC input wire sizes listed in Table 3‐4 on page 3-14, Table 3‐5 on page 3-15, Table 3‐6 on page 3-16
and Table 3‐7 on page 3-17 the DC terminations listed in Table 3‐11 on page 3-20, type of battery installation, and requirements from NEC Table 4,
Electrical Metallic Tubing (EMT).
NOTE 2
Because of the future upgradability to a fully rated 825 kVA UPS with the addition of the FI-UPM, these conduit sizes are specified for an
825kVA UPS.
NOTE 3
Bypass conduit data is not applicable to IOM configurations.
Содержание Powerware 9395
Страница 2: ......
Страница 28: ...Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality 2 2 ...
Страница 134: ...Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality 5 20 ...
Страница 254: ...WARRANTY Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality W 2 ...
Страница 255: ......
Страница 256: ... 1642017254 164201725 4 ...