UPS OPERATING INSTRUCTIONS
Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual
S
164201725 Rev 4
www.eaton.com/powerquality
7-33
7.4.3
Disable Energy Saver System Mode from the UPS Command Menu
To disable Energy Saver System mode:
NOTE
The Energy Saver System mode commands are displayed only if enabled at the factory or by an
Eaton Customer Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are mutually exclusive.
If the Variable Module Management System mode is enabled, the Energy Saver System mode commands will
not be displayed.
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status
screen is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS
Control Command screen is displayed.
4.
On the UPS Control Command screen, select
DISABLE ENERGY SAVER
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS transfers to Battery mode and then to Online mode.
The Online status indicator is illuminated. The UPS status indicates
ONLINE
. The
UPM status indicates
ONLINE
.
7.4.4
Start Energy Saver System High Alert Mode from the UPS Command
Menu
To start High Alert mode:
NOTE
The High Alert mode commands are displayed only if enabled at the factory or by an Eaton Customer
Service Engineer.
NOTE
The Variable Module Management System and Energy Saver System modes are mutually exclusive.
If the Variable Module Management System mode is enabled, the Energy Saver System mode commands will
not be displayed.
1.
Press the
CONTROLS
pushbutton on the main menu bar. The System Status
screen is displayed.
2.
On the System Status screen, select the
UPS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The UPS
Control Command screen is displayed.
4.
On the UPS Control Command screen, select
START HIGH ALERT
.
5.
Press the
SELECT
pushbutton on the UPS Command menu bar.
The UPS starts High Alert mode with the UPMs online supplying the critical load.
After one hour the UPS transfers to Energy Saver System mode.
The Online status indicator is illuminated. The UPS status indicates
HIGH
ALERT
. The UPM status indicates
ONLINE
. The power module is on.
Содержание Powerware 9395
Страница 2: ......
Страница 28: ...Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality 2 2 ...
Страница 134: ...Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality 5 20 ...
Страница 254: ...WARRANTY Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality W 2 ...
Страница 255: ......
Страница 256: ... 1642017254 164201725 4 ...