INTRODUCTION
Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual
S
164201725 Rev 4
www.eaton.com/powerquality
1-4
1.1
UPS Standard Features
The UPS has many standard features that provide cost‐effective and consistently
reliable power protection. The descriptions in this section provide a brief overview of
the UPS standard features.
1.1.1
Installation Features
Each UPS section is shipped separately. The sections are mechanically and electrically
joined at the installation site, and can be permanently bolted to the floor.
Power wiring can be routed through the top or bottom of the cabinet with
connections made to easily accessible terminals. Control wiring is routed through the
top of the cabinet and must be installed in accordance with Class 1 wiring methods.
1.1.2
Control Panel
The control panel, located on the front of the UPS, contains a liquid crystal display
(LCD) and pushbutton switches to control the operation of the UPS and to display the
status of the UPS system. See Chapter 7, “UPS Operating Instructions,” for
additional information.
1.1.3
Customer Interface
S
Building Alarm Monitoring
– Up to five inputs in the UPS are available to connect the
facility's alarm system contacts. Some system configurations may limit the number
of inputs available. The UPS uses these inputs to monitor the building alarms in
addition to the UPS status. See Chapter 8, “Communication,” for additional
information.
S
Alarm Contact
– One alarm contact is provided for connection to equipment at the
facility, such as a light, an audible alarm, or a computer terminal. The equipment
connected to this contact alerts you to a UPS alarm. See Chapter 8,
“Communication,” for additional information.
S
X-Slot Communication Bays
– Four communication bays are standard equipment.
One to four optional X-Slot
®
connectivity cards can be installed in the UPS module
at any time. X-Slot cards are quickly installed at the front of the UPS and are
hot-pluggable. See Chapter 8, “Communication,” for additional information.
1.1.4
Advanced Battery Management
A three-stage charging system increases battery service life by optimizing recharge
time, and protects batteries from damage due to high current charging and inverter
ripple currents. Charging at high currents can overheat and damage batteries.
1.1.5
Power Management Software
LanSafe
®
Power Management Software is bundled as part of the Software Suite CD
shipped with the UPS. See Chapter 8, “Communication,” for additional information.
Содержание Powerware 9395
Страница 2: ......
Страница 28: ...Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality 2 2 ...
Страница 134: ...Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality 5 20 ...
Страница 254: ...WARRANTY Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality W 2 ...
Страница 255: ......
Страница 256: ... 1642017254 164201725 4 ...