UPS OPERATING INSTRUCTIONS
Eaton 9395 UPS (450–825 kVA) Installation and Operation Manual
S
164201725 Rev 4
www.eaton.com/powerquality
7-42
16.
Verify the following messages display sequentially on the UPM status line:
DC STARTING, CHARGER OFF
INVERTER STARTING
INVERTER SYNCING
READY
The UPM rectifier and inverter turn on.
17.
To transfer the UPM to Online mode, press the
CONTROLS
pushbutton on the UPS
Control Command menu bar. The UPM Control Command screen is displayed.
18.
On the UPM Control Command screen, select
UPM GO TO ONLINE
.
19.
Press the
SELECT
pushbutton on the UPM Command menu bar.
The UPM transfers to Online mode. The UPM status indicates
ONLINE
.
7.4.17
Transfer from Online to Bypass Mode
To transfer the critical load to Bypass mode:
C
A
U
T
I
O
N
In Bypass mode, the critical load is not protected from commercial power interruptions and abnormalities.
1.
On any UPS, press the
CONTROLS
pushbutton on the main menu bar. The System
Status screen is displayed.
2.
On the System Status screen, select the
BYPASS
command.
3.
Press the
CONTROLS
pushbutton on the System Status menu bar. The Bypass
Control Command screen is displayed.
4.
On the Bypass Control Command screen, select
GO TO BYPASS
.
5.
Press the
SELECT
pushbutton on the Bypass Command menu bar.
All of the UPSs transfer to Bypass mode and the critical load is immediately
supplied by the bypass source. If the bypass source is not available, the power
module remains on and an alarm sounds.
The
BYPASS
status indicator is illuminated. The Bypass status indicates
ON
. The
UPM status indicates
READY
. The power module remains on.
W
A
R
N
I
N
G
Power is present inside the UPS cabinet.
7.4.18
Transfer from Bypass to Online Mode
To transfer the critical load to Online mode:
1.
If not already closed, close the battery breaker.
2.
On any UPS, press the
CONTROLS
pushbutton on the main menu bar. The System
Status screen is displayed.
Содержание Powerware 9395
Страница 2: ......
Страница 28: ...Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality 2 2 ...
Страница 134: ...Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality 5 20 ...
Страница 254: ...WARRANTY Eaton 9395 UPS 450 825 kVA Installation and Operation Manual S 164201725 Rev 4 www eaton com powerquality W 2 ...
Страница 255: ......
Страница 256: ... 1642017254 164201725 4 ...