IB02602002E
SECTION 6 - INSTallaTION aND WIRING
6.0 Mounting the MP-4000 Motor Protection Relay
The following subsections describe the mounting of the MP-4000 mo
-
tor protection relay, and its optional URTD and PONI communications
modules.
6.0.1
Mounting locations
Mount the unit vertically on a flat panel. The location should be as free
as possible of water, chemicals, dust, and excessive heat and vibra
-
tion. The panel should protect the User from accidental contact with
live terminals on the back of the MP-4000. A 0.125-in. (3.2-mm) steel
panel or door, solidly grounded, is recommended.
Before actually cutting the panel, check the required three-dimen
-
sional clearances for the MP-4000 case, particularly behind the panel.
Figures 6.3 and 6.4 show these clearances. If mounting the unit on a
swinging door, check the swinging clearance of rear projections and
wired connections.
Figure 6.2 shows dimensions for the panel cutout and mounting holes.
Cutout tolerances and mounting screw hole placement are critical. In
particular, the tolerance of the horizontal dimension between the center
of the mounting holes and the vertical edge of the cutout must be
between 0 and +0.050 in. (1.273 mm).
NOTE:
The cutout is the same as for the previous-generation IQ 1000
II and MP-3000 motor relays, and other Eaton, Inc. IQ products
of this case size. The six mounting holes that secure these
older products are still correctly located for the MP-3000, but
the four additional new holes should be added.
Secure the MP-4000 to the panel with the special self-tapping plastic
screws using moderate torque - 8 in.-lbs (0.9 N-m). Use the 0.375-in.
(9.5-mm) long screws supplied with the MP-4000 to mount the unit on
a 0.125-in. (3.2-mm) panel. Do not attempt to tap the screw holes, and
do not use machine screws.
6.0.2
Mounting the URTD Module
The optional URTD module provides temperature data to the MP-4000
from up to 11 RTDs embedded in the motor and driven equipment.
Refer to URTD I.L. 17367 for further information.
The URTD module may be mounted either on the back of the MP-4000
by using the URTD mounting bracket and machine screws (supplied
with the URTD module), or mounted remotely from the MP-4000. If
mounting the URTD module on the back of the MP-4000, see Figure
6.4 for overall depth dimensions. Figure 6.5 shows the URTD stand-
alone mounting dimensions.
Consider the benefit of mounting the URTD module away from the
MP-4000, as close as possible to the motor. The RTD wiring, consist-
ing of a large bundle of wires, is thus much shorter. The URTD con
-
veys multiplexed temperature data back to the MP-4000 via a single
optical fiber (recommended), or by a 3-wire communications conductor.
The URTD may be placed up to 400 ft (121.9 m) from the MP-4000
with the optical fiber connection (recommended), or up to 499 ft
(152 m) away with a wired communications connection. Note that the
URTD requires 120 Vac power (6 VA) at its remote location. It may be
mounted in any orientation.
6.0.3
Mounting the PONI Communications Module
Refer to Section 10 for a description of the various types of optional
PONI communications modules that can be used with the MP-4000.
Check the I.L. for the selected PONI to confirm dimensions and com
-
munications network connection requirements.
Figure 6.4 shows clearance dimensions to the rear of an I-PONI, M-
PONI, or D-PONI. An E-PONI is 0.5 in. (12.7 mm) deeper.
The PONI, if used, is always mounted on the back of the MP-4000. If
no URTD is mounted there, use the mounting bracket supplied with
the MP-4000, as shown in Figure 6.4. The bracket gives a conve
-
nient space to run CT wires underneath the PONI to the adjacent CT
terminal block.
If a URTD is mounted on the back of the MP-4000, the PONI pig
-
gybacks directly to the URTD module as shown. Use the machine
screws supplied with the PONI in the molded plastic mounting holes of
the URTD.
6.1 Wiring - General Information
When routing wires between the starter and the associated machine
or process equipment, follow these guidelines:
Do not route the control or RTD wiring through the high-volt
-
age compartment of the motor starter. However, the starter
manufacturer may be able to recommend or provide specific
measures for doing this if it is really necessary.
Separate the lower voltage (120 Vac) from the higher volt-
age (440 Vac or higher) conductors as much as possible. In
general, maintain a minimum distance of 1.5 feet (45 cm)
between the two types.
Any low-voltage control wiring routed out of the motor
starter cabinet should be at least #14 AWG (2.6 mm
2
)
stranded copper wire.
Communications circuits may use thinner conductors, as
recommended in installation literature for those circuits.
WaRNING
BEFORE WORKING WITh ThE WIRING, MaKE SURE POWER IS
DISCONNECTED FROM ThE MOTOR STaRTER, MP-4000, aND
all REMOTE CONNECTIONS, INClUDING CONTaCT OUTPUT
CONTROl CIRCUITS aND REMOTE INPUT CONTaCTS. OTh-
ERWISE, haZaRDOUS VOlTaGES COUlD CaUSE INjURy
OR DEaTh. alSO, UNEXPECTED MOTOR CONTROl aCTION
COUlD INjURE PERSONNEl OR DESTROy EQUIPMENT.
Figure 6.6 shows rear terminal connections of the MP-4000.
Connect terminal 5 to the closest solid electrical-safety grounding
point with a heavy wire or braid (#14 AWG [2.6mm
2
] or larger). Do not
use a current-carrying or neutral conductor for this grounding. Also,
do not tie terminal 5 to neutral terminal 7 at the relay. Note that termi
-
nal 5 is internally connected to the outer case and to the conductive
faceplate of the relay.
6.1.1
CT Wiring
Carefully read the advice in Subsection 5.1.5 on the choice of CT
ratios for a particular motor application. An inappropriate CT ratio re
-
sults in poor measurement accuracy and limited protection. More seri
-
ous errors in ratio choice make it impossible to set the relay properly.
Connect the phase and optional ground CTs as shown in Figures 6.7,
6.8, and 6.9. Pay attention to the phase identification and sequence,
and check for consistent polarity among the three phases. The
MP-4000 may not allow the motor to run, and cannot protect the mo
-
tor properly, if two phases are swapped or if the polarity of any CT is
reversed with respect to the other two.
Pass the motor phase conductors through the window of the flux-
canceling ground CT. The ground CT need not have any particular
polarity relationship to the phase CTs.
•
•
•
•
Содержание MP-4000
Страница 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Страница 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Страница 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Страница 62: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 4 MP 4000 Case Depth Dimensions DIMENSIONS IN INCHES CM...
Страница 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Страница 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Страница 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Страница 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Страница 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Страница 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Страница 86: ...Page 9 10 www eaton com IB02602002E MP 4000 Figure 9 4 Motor Protection Curve Example without RTDs...
Страница 87: ...www eaton com Page 9 11 MP 4000 IB02602002E Figure 9 5 Motor Protection Curve Example with RTDs...
Страница 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Страница 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Страница 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...