www.eaton.com
Page
3-1
MP-4000
IB02602002E
SECTION 3 - MP-4000 TEChNICal SPECIFICaTIONS
Control Power
Nominal Voltage:
120 Vac or 240 Vac
(+10%, –25%)
Operating Range:
120 Vac: 90 - 132 Vac
240 Vac: 180 - 264 Vac
Interruption Ride Through Time:
Complete drop of power for
minimum of 13 cycles at
nominal 60 Hz control power
voltage, and 11 cycles
at nominal 50 Hz control
power voltage.
Frequency:
60 Hz nominal, 57-63 Hz
50 Hz nominal, 47-53 Hz
Power Consumption:
24 VA max
URTD: 6 VA max.
IPONI: 1 VA max.
Current Inputs
Nominal (I
n
):
1 A or 5 A
CT Rating:
2 x I
n
continuous
50 x I
n
for 1 sec.
CT Burdens:
< 0.25 VA @ 5 A (nominal)
< 0.05 VA @ 1 A (nominal)
Voltage Inputs
Nominal:
120 Vac
Range:
69-150 Vac
Metering accuracy
Phase Current Accuracy:
± 1% of I
n
(from 0 to I
n
A)
± 1% of reading
(from I
n
to I0I
n
A)
Ground Current Accuracy:
± 1.5% of I
n
(0 to 55% of I
n
A)
± 2% of I
n
(55% I
n
to I
n
A)
± 2% of reading (from I
n
to
4 I
n
A)
Phase Voltage Accuracy:
± 1% of reading, 3 V min.
Phase Angle Accuracy:
± 1° of reading (P
f
= 1)
Power Accuracy:
± 5% of reading (0.5 < P
f
< 1)
Discrete Inputs
Number of inputs:
2 programmable
Rating:
1.2 VA @ 120 Vac
Max. off = 36 Vac
Min. on = 86 Vac
Output Contacts
Number of Outputs:
4 form C, programmable
Momentary:
Make 30 A ac/dc for 0.25 sec.
Break 0.25 A @ 250 Vdc
(resistive)
Break 5 A @ 120/240 Vac
Continuous:
5A @ 120/240 Vac
5A @ 30 Vdc
analog Output
Rating:
± 4 to 20 mA, programmable
Max Load:
1 kilohm
Accuracy:
1%
Motor Overload Protection (I
2
t)
Full Load Amps:
10 to 3,000 A
Locked Rotor Current:
300 to 1,200% FLA
Locked Rotor Time:
1 to 120 sec.
Ultimate Trip Current:
85 to 150% FLA
Phase CT Ratio:
10 to 4,000: I
n
Ground CT Ratio:
10 to 4,000: I
n
Timing Accuracy:
The greater of ± 2.5% or ± 100
ms for current > 1.1 X UTC
Trip Setting Ranges
Ground Fault (GF):
Off, 2% to 55% of CT ratio
primary
GF Start Delay:
2 to 60 cycles
GF Run Delay:
0 to 60 cycles
Timer Accuracy:
± 2.5 cycles, -1/2 cycle
Instantaneous Overcurrent:
Off, 300 to 1,600% FLA
IOC Start Time Delay:
2 to 60 cycles
Timer Accuracy:
± 2.5 cycles, -1/2 cycle
Jam Trip:
Off, 100 to 1,200% FLA
Underload Trip:
Off, 6 to 90% FLA
Phase Unbalance Trip (I):
Off, I
2
/I
1
= 4 to 40%
Start Delay Timers:
0 to 120 sec. – underload and
phase unbalance
0 to 1,200 sec. - jam
Run Delay Timers:
0 to 240 sec.
Timer Accuracy:
± .5% + 250 ms
For phase unbalance, add 200
ms for zero setting
For underload, add 480 ms for
zero setting
Phase Unbalance V
Trip:
1 to 100 V, Off
Trip Run Delay:
1 to 480 sec., Off
Trip and Alarm Start Delay:
0 to 480 sec., Off
Underfrequency
Trip Threshold:
15 to 60 Hz, Off
Trip Run Delay:
0 to 60 sec., Off
Trip and Alarm Start Delay:
0 to 60 sec., Off
Overfrequency
Trip Threshold:
15 to 70 Hz, Off
Trip Run Delay:
0 to 60 sec., Off
Trip Alarm Start Delay:
0 to 60 sec., Off
Overvoltage
Main Trip Threshold:
10 to 150 V, Off
Main Run Delay:
0 to 480 sec., Off
Neutral Trip Threshold:
10 to 150 V, Off
Undervoltage
Main Undervoltage Threshold:
10 to 150 V
Main UV Trip Run Delay:
0 to 60 sec.
Main Undervoltage Threshold:
10 to150 V
Under Voltage Start Delay:
0 to 60 sec.
Ratio of V2 to V1:
4% to 40%
Underpower
Underpower Trip Threshold:
0.06 to 0.90 *FLA*VT
Underpower Trip/Alarm Start Delay: 0 to 60 sec.
Underpower Trip Run Delay:
0 to 480 sec.
Leading PF Trip:
0.05 to 0.99
Lagging PF Trip:
0.05 to 0.99
PF Trip Start Delay:
0 to 60 sec.
PF Trip Run Delay:
0 tp 60 sec.
Содержание MP-4000
Страница 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Страница 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Страница 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Страница 62: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 4 MP 4000 Case Depth Dimensions DIMENSIONS IN INCHES CM...
Страница 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Страница 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Страница 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Страница 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Страница 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Страница 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Страница 86: ...Page 9 10 www eaton com IB02602002E MP 4000 Figure 9 4 Motor Protection Curve Example without RTDs...
Страница 87: ...www eaton com Page 9 11 MP 4000 IB02602002E Figure 9 5 Motor Protection Curve Example with RTDs...
Страница 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Страница 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Страница 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...