www.eaton.com
Page
4-5
MP-4000
IB02602002E
Table 4-2. Monitor Mode Display.
SUB-
MENU
LINE
DISPLAY
COMPLETE HELP MESSAGE
DESCRIPTION
10
LT2 XXXX
LOAD BEARING TEMP 2 IN DEGREES
F or C
RTD reading - terminals 29, 30, 31.
11
AXT XXXX
AUXILIARY TEMP IN DEGREES F or C
RTD reading - terminals 33, 34, 35.
MONT
MTR
REAL TIME MOTOR DATA
Motor monitoring data follows.
1
VER XXXX
SOFTWARE VERSION NUMBER
MP-4000 software version in use.
2
%I2T XXX
PERCENT OF I2T TRIP LEVEL
Percentage of thermal bucket used.
3
TUS XXX
TIME IN MINUTES UNTIL NEXT START CAN OCCUR
Displays largest amount of time in minutes among
three functions: anti-backspin, starts per unit time
and time between starts.
4
RMST XX
REMAINING STARTS
Number of starts remaining if starts per time is programmed.
5
OST XXX
TIME LEFT ON OLDEST START IN MINUTES
Remaining time allowed on oldest start for starts per time if
programmed. If motor start/time is exceeded, this is time in minutes
before restart is permitted.
6
ICM XXXX
ADDRESS ON THE IMPACC NETWORK IN HEXADECIMAL
Address of device if on INCOM communications network; only visible
if on network.
7
DI 1 OFF or
DI 1 ON
STATE OF DISCRETE INPUT 1
Current state of discrete input 1; ON = 120 Vac present, OFF =
120 Vac not present.
8
DI 2 OFF or
DI 2 ON
STATE OF DISCRETE INPUT 2
Current state of discrete input 2; ON = 120 Vac present, OFF =
120 Vac not present.
MONT
TIM
DATE AND TIME
Current date and time with display format as programmed.
1
HH.MM XM
CURRENT TIME
12-hour format.
or
or
HH.MM
24-hour format.
2
MM/DD/YY
CURRENT DATE
Common format
or
or
DD/MM/YY
European / military format.
MONT V
REAL TIME DATA FROM VOLTAGE RMS MEASUREMENTS
1
VA XXXX
PHASE A TO GROUND VOLTAGE
VAG RMS phase voltage.
2
VB XXXX
PHASE B TO GROUND VOLTAGE
VBG RMS phase voltage.
3
VC XXXX
PHASE C TO GROUND VOLTAGE
VCG RMS phase voltage.
4
VG XXXX
GROUND VOLTAGE
Neutral voltage differential (neutral to ground).
5
VPAV XXXX
AVERAGE OF PHASE VOLTAGES
Average of the RMS line to neutral voltages
VL avg. (Va+Vb+Vc)/3).
6
VAB XXXX
LINE TO LINE VOLTAGE VAB
RMS line to line voltage VAB.
7
VBC XXXX
LINE TO LINE VOLTAGE VBC
RMS line to line voltage VBC.
8
VCA XXXX
LINE TO LINE VOLTAGE VCA
RMS line to line voltage VCA.
9
VLAV XXXX
AVERAGE OF THE LINE TO LINE
VOLTAGES
VLL average.
10
FRQ XXXX
MEASURED FREQUENCY
Frequency as measured on phase A voltage input.
MONT
VSQ
REAL TIME DATA FROM SEQUENCE VOLTAGES PHASOR
MEASUREMENTS
1
V1MG XXXX
V1 PHASOR MAGNITUDE
Magnitude of positive sequence voltage.
2
V2MG XXXX
V2 PHASOR MAGNITUDE
Magnitude of negative sequence voltage.
3
3V0 XXXX
3V0 PHASOR MAGNITUDE
Magnitude of zero sequence voltage.
4
V1AG XXXX
V1 PHASE ANGLE
Phase angle of positive sequence voltage.
5
V2AG XXXX
V2 PHASE ANGLE
Phase angle of negative sequence voltage.
6
V0AG XXXX
V0 PHASE ANGLE
Phase angle of zero sequence voltage.
7
%VUB XXXX
VOLTAGE PHASE UNBALANCE - IF POSITIVE THE RATIO OF
NEGATIVE TO POSITIVE SEQUENCE VOLTAGE - IF NEGATIVE
THE INVERSE
Voltage unbalance.
Содержание MP-4000
Страница 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Страница 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Страница 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Страница 62: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 4 MP 4000 Case Depth Dimensions DIMENSIONS IN INCHES CM...
Страница 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Страница 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Страница 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Страница 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Страница 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Страница 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Страница 86: ...Page 9 10 www eaton com IB02602002E MP 4000 Figure 9 4 Motor Protection Curve Example without RTDs...
Страница 87: ...www eaton com Page 9 11 MP 4000 IB02602002E Figure 9 5 Motor Protection Curve Example with RTDs...
Страница 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Страница 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Страница 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...