MP-4000
IB02602002E
Table 4-3. View Setting Mode/Program Worksheet.
SUB-
MENU
LINE #
DISPLAY
HELP MESSAGE
SETTING RANGE/VALUE
(DEFaUlT SElECTION aND
ValUE aS ShIPPED IN BOlD)
VALUE SELECTED
VIEW SP
VIEW PROGRAM SETTINGS
PaGE 1, SP MOTOR SETTINGS FOR MOTOR CONSTaNTS
1
FLA XXXX
FULL LOAD AMPS
10-3,000 amps in 1 amp. increments
(10)
2
LRC XXXX
LOCKED ROTOR CURRENT % OF FLA
300-1,200% in 1% increments
(300)
3
LRT XXX
MAXIMUM ALLOWABLE STALL TIME IN
SECONDS
1-120 sec. in 1 sec. increments
(
300)
4
UTC XXX
ULTIMATE TRIP CURRENT IN %FLA
85-150% in 1% increments
(1)
5
PCT XXXX
PHASE CT RATIO NUMERATOR IN
PRIMARY AMP
10-4,000 A in increments of 1
(10)
6
GCT XXXX
GROUND CT RATIO NUMERATOR IN
PRIMARY AMP
10-4,000 A in increments of 1
(50)
7
FREQ 50
or FREQ 60
50 - FOR 50 HERTZ LINE FREQUENCY
60 - FOR 60 HERTZ LINE FREQUENCY
Toggles between FREQ 50 and
FREQ 60
8
REV or NON
REV
REVERSING OR NON REVERSING
STARTER
Toggles between REV and
NON REV
9
STOP X
MOTOR STOP CURRENT LEVEL IN
% OF PHASE CT RATIO NUMERATOR
2-20% of phase CT ratio numerator in 1%
increments
(5%)
PaGE 2, SP RTD SETTINGS FOR RTD INPUTS
1
RTD IN C
or
RTD in F
DISPLAYED IN DEGREES C OR F
Toggles between
RTD IN C
and RTD IN F
2
WD T XXX
WINDING TEMP TRIP
0-199 C, OFF/32-390 F, OFF in 1 increments
(100)
3
WD A XXX
WINDING TEMP ALARM
0-199 C, OFF/32-390 F, OFF in 1 increments
(80)
4
MB T XXX
MOTOR BEARING TRIP
0-199 C, OFF/32-390 F, OFF in 1 increments
(100)
5
MB A XXX
MOTOR BEARING ALARM
0-199 C, OFF/32-390 F, OFF in 1 increments
(80)
6
LB T XXX
LOAD BEARING TRIP
0-199 C, OFF/32-390 F, OFF in 1 increments
(80)
7
LB A XXX
LOAD BEARING ALARM
0-199 C, OFF/32-390 F, OFF in 1 increments
(80)
8
AX T XXX
AUXILIARY TRIP
0-199 C, OFF/32-390 F, OFF in 1 increments
(100)
9
AX A XXX
AUXILIARY ALARM
0-199 C, OFF/32-390 F, OFF in 1 increments
(80)
10
DIAG ON
or
DIAG OFF
ALARM ON RTD FAILURE DIAGNOSTIC
Toggles between
DIaG ON
and DIAG OFF
PaGE 3, SP TRIP SETTINGS FOR TRIP EVENTS
1
GFT XXX
GROUND FAULT TRIP LEVEL IN % OF
GROUND CT RATIO NUMERATOR
2-55% OF Ground CT ration numerator, OFF
(1% increments)
(24%)
Program Date
Control Schematic
Unit ID/Starter Type
Work Order #
Motor HP
Mfgr.
Serial #
Volts
FLA
LRC
Stall Time/LRT
Accel. Time
SF
RTD Type
Other
Содержание MP-4000
Страница 6: ...Page vi www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Страница 56: ...Page 5 16 www eaton com IB02602002E MP 4000 This page intentionally left blank...
Страница 60: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 2 Panel Cutout Dimensions...
Страница 62: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 4 MP 4000 Case Depth Dimensions DIMENSIONS IN INCHES CM...
Страница 64: ...Page 6 www eaton com IB02602002E MP 4000 Figure 6 6 Rear Panel Terminals...
Страница 67: ...www eaton com Page 6 11 MP 4000 IB02602002E Figure 6 11 Alternatives for Discrete Input Wiring...
Страница 72: ...Page 7 www eaton com IB02602002E MP 4000 This Page Intentionally Left Blank...
Страница 83: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 1 Rotor Temperature Tracking...
Страница 84: ...Page 9 www eaton com IB02602002E MP 4000 Figure 9 2 Motor Protection Curve...
Страница 85: ...www eaton com Page 9 MP 4000 IB02602002E Figure 9 3 Underload Jam Protection Curve...
Страница 86: ...Page 9 10 www eaton com IB02602002E MP 4000 Figure 9 4 Motor Protection Curve Example without RTDs...
Страница 87: ...www eaton com Page 9 11 MP 4000 IB02602002E Figure 9 5 Motor Protection Curve Example with RTDs...
Страница 88: ...Page 9 12 www eaton com IB02602002E MP 4000 Figure 9 6 Motor Start and Run Cycles...
Страница 110: ...Page 13 10 www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...
Страница 111: ...www eaton com MP 4000 IB02602002E This Page Intentionally Left Blank...