EATON ELECTRICAL
56
Predictive Diagnostics
may be used for synchronization.
Sensor interface board with jumpers is shown in the figure 6.2a. Enlarged portions of the board are in the
figures 6.2 b and c. Jumper positions as they are shown (default) configure external reference for a
coupling capacitor. Arrows show default position of the jumpers. In this case power frequency signal
component from PD channel #1 is brought to the “Ref” terminal #8 and may be used for both external
synchronization and phase reference shift measurement.
In order to use “Ref” terminal for an external signal, the jumpers J1 and J2 should be removed
disconnecting “Ref” from PD channel #1.
a.
b.
c.
Figure 6.2 Default jumper position as shown. Pre-Revision 1.
6.1.2 Revision 1
As default, jumpers in the sensor interface board are configured for synchronization from power
frequency signal component of the channel #1. This assumes that coupling capacitor sensor from the
phase A is connected to this channel. Therefore, once jumpers in IG are moved to external
synchronization option, as it described in 6.1 (the figure 6.1) above, IG will be synchronized from PD
sensor connected to the channel 1. Jumper J1 actually connects this input to synchronization circuitry.
Refer to the figure 6.3 for jumper locations.
Jumpers
J1 & J2
Jumpers
J4 & J5
Jumper J3