EATON ELECTRICAL
27
Predictive Diagnostics
TB1 (Sensor interface board)
##
All revisions
Note
1&2
PD#01 signal(1)&shield(2)
Coax Cable RG-58
3&4
PD#02 signal(3)&shield(4)
Coax Cable RG-58
5&6
PD#03 signal(5)&shield(6)
Coax Cable RG-58
7&8
PD#04 signal(7)&shield(8)
Coax Cable RG-58
9&10
PD#05 signal(9)&shield(10)
Coax Cable RG-58
11&12
PD#06 signal(11)&shield(12)
Coax Cable RG-58
13&14
PD#07 signal(13)&shield(14)
Coax Cable RG-58
15&16
PD#08 signal(15)&shield(16)
Coax Cable RG-58
17&18
PD#09 signal(17)&shield(18)
Coax Cable RG-58
19&20
PD#10 signal(19)&shield(20)
Coax Cable RG-58
21&22
PD#11 signal(21)&shield(22)
Coax Cable RG-58
23&24
PD#12 signal(23)&shield(24)
Coax Cable RG-58
25&26
PD#13 signal(25)&shield(26)
Coax Cable RG-58
27&28
PD#14 signal(27)&shield(28)
Coax Cable RG-58
29&30
PD#15 signal(29)&shield(30)
Coax Cable RG-58
31&32
Noise#16 signal(31)&shield(32)
Coax Cable RG-58
TB3 (Sensor interface board)
##
Pre-Revision 1
Revision 1
Note
1.
RTD common wire
Same
For two-wire RTD terminal 1
should shortened with the
terminal 2
2.
RTD common wire
Same
3.
RTD signal wire
Same
4.
Current sensor common wire
RTD cable shield
5.
Current sensor signal wire
Same
Never exceed 0.6V AC! Must
be isolated from the ground at
the sensor location!
Input Impedance 100/110
Ohms.
6.
Voltage sensor or Reference
sensor or Humidity common
wire
Current sensor common wire
7.
Voltage sensor signal wire
Normally not Used!
External Reference signal.
Normally not Used!
1. In Pre Rev 1 Input
impedance 2kOhm, signal
should not exceed 6VAC
2. Rev 1 Input Impedance
1MOhm, signal should not
exceed 6VAC
8.
Reference sensor signal wire
Control Point. Not Used.
9.
Reserved
Humidity Sensor cable shield
10.
Reserved
Humidity Sensor common wire
11.
+5 Volt for humidity sensor
Same
For H% sensor only
12.
Humidity sensor signal wire
Same
For H% sensor only
Panel Terminal Strip
Pin
##
Pre-Revision 1
Revision 1
Note
1.
G - External AC power Ground
Same