EATON ELECTRICAL
48
Predictive Diagnostics
P3
– Green (normal) threshold for Magnitude @0.2 ppc (mV)
P4
– Yellow (warning) threshold for Magnitude @0.2 ppc (mV)
P5
– Red (alarm) threshold for Magnitude @0.2 ppc (mV)
List of status thresholds for trend:
P0
– Yellow (warning) threshold for trend (times per year). Recommended 3-5times/year.
P1
– Red (alarm) threshold for trend (times per year). Recommended 5-10times/year.
Level Alarm thresholds. PDI and Q
02
Yellow, Red, and Green thresholds for each channel.
Scroll setup parameters until
tHrESH
appears.
Press
Enter. CH01
will appear. Press
Enter
.
P0-00005
will appear. You are now ready to enter the
threshold for parameter
P0
. Use
keys to change the threshold numerical value (refer to
respective units below).
When done, press
Enter
.
Use
keys to select another parameter and repeat the setup procedure.
When done, press
Esc
. Use
keys to select another channel and repeat.
Trend Alarm thresholds. Yellow and Red thresholds (this setting is the same for all channels).
Scroll setup parameters using
until
trEnd
will appear.
Press
Enter
.
P0-010.00
will appear. Press
Enter
.
Digit will start flashing. Using
keys to
change the threshold numerical value (refer to respective units below).
Press
key and
P1-020.00
will appear. Press
Enter
.
Digit will start flashing. Using
keys to
change the threshold numerical value (refer to respective units below).
When done, press
Enter
.
Press
Esc
.
When done with all thresholds setting, press
Esc
.
Rated Voltage:
Object under test rated voltage is used for calculation of partial discharge intensity. Set rated voltage line-
to-line in terms of kV.
Scroll setup parameters until
VOLtAGE
appears.
Press
Enter
.
VOL-013.8
will appear. Use
keys to set rated voltage of monitored object (kV,
line-to-line).
When done, press
Enter
.
Rated Current:
Scroll setup parameters until
CurrEnt
appears.
Press
Enter
.
I-00001.0
will appear. Use
keys to set the rated current of the object under
test in A (usually full load or nominal current).
When done, press
Enter
.
Number of Power Cycles for Data Acquisition:
This setting determines the length of time the device will acquire data to get sufficient statistical PD
representation. The parameter is measured in terms of number of cycles of power frequency. 60 cycles is
recommended for rotating machines and 120 cycles for switchgear.
Scroll setup parameters until
SinCount
appears.
Press
Enter
.
Cnt-06
will appear. Use
keys to set the number of power cycles (of 60 or 50 Hz) for
the measurement.
When done, press
Enter
.
Alarm Relay Mode:
Alarm Relay can be set in one of three modes:
Disabled (
OFF
) – Relay will not close contacts in a case of alarm