EATON ELECTRICAL
40
Predictive Diagnostics
should be entered in manual mode.
Important Note! In the firmware version 2.07 ONLY!
Automatically detected phase shift MUST be manually
correctet by subtracting detected value from 360 Deg!
Than follow this manual with newly determined
number.
Measurement
Schedule
The device is shipped with a schedule enabled of four
measurements a day. This is the factory default setting.
If needed, a single measurement can be done any time
by a command from a PC.
There is an option to set measurements by time
interval. Remember: the interval can not be less then
a time of single measurement!
To estimate a time of a measurement use the formula
t= N
cycle
*N
ch
*21/60 +1 minute, N
cycle
– number of
power cycles, N
ch
– number of active channels. Never
set time interval in minutes less, then calculated by
the formula. Otherwise, you might create an infinite
cycle and will not be able to get out without
rebooting.
Scroll setup parameters until
trEAdinG
appears.
Press
Enter
.
rEG-dt
will appear. Use
keys to schedule the
measurement by a time interval
rEG-dt
or a fixed time of a day
rEG-t
.
When done, press
Enter
.
Select
rEG-dt
and press
Enter
.
Set time interval in format XX.XX (hh.mm) using
keys.
Military format (24 hour) is used. Maximum interval can be 23 hours and
50 minutes.
Press
Enter
.
OR
Select
rEG-t
and press
Enter
.
t01-00.00
will appear.
Set
t01
to a desired time in the (hh.mm) format using
keys.
Press
Enter
when finished with
t01
.
Use
keys to select
t02
to the desired time. Continue until the
required number of daily measurements specified.
When finished with all time settings, press
Esc
.
Save Mode
As default, the device is shipped with “Brief” mode of
data saving. That will save a full PRPDD matrixes only
twice a month. For commissioning one might need
“Full” save mode for single measurements.
Remember:
Set it back to Brief when finished!
Scroll setup parameters until
SET SAVE
appears.
Press
Enter
.
S-briEF
will appear.
Use
keys to select
S-briEF
or
S-FULL
mode.
When done, press
Enter
.
Alarm Relay
Mode
Alarm Relay can be set in one of three modes:
1. Disabled (
OFF
) – Relay will not close contacts in a
case of alarm
2. Enabled (
On
) – Relay will keep alarm contacts
closed all the time while alarm conditions are
present
3. Enabled for Time (
t
) – Relay contacts will be closed
Scroll setup parameters until
rELAY
appears.
Press
Enter
.
rELE-On
will appear.
Using
keys select
On, OFF, or t
Press
Enter
.
In case
On or OFF
was selected, the setting will be stored.
In case
t
was selected,
t-0000
will appear. Using
set time for
relay closing in seconds.