Predictive Diagnostics
•
In panel installations check for the presence of a 1A fuse. Replace with,
5x20 mm ,
1.0 Amp, 250VAC . (We recommend 195 Series –(By Wickmann). Digi-Key part
number – WK5048-ND).
In a separately delivered InsulGard (for front installation)
plug 115/230V power cord (supplied with the device) into the power connector at the
bottom right of InsulGard.
•
Energize the external power supply circuit (in a separately delivered InsulGard for
front installation plug the InsulGard cord into an outside 115/230V AC receptacle).
“Loading” should appear on the device display. Device is now ready for setup and
operation. In a panel installed design check additionally that 115/230V is present in a
receptacle inside the enclosure.
•
In a panel-installed device with added power module and modem or converter power
will be applied to them simultaneously with energizing the InsulGard. If modem and
power source are mounted on a separate panel, as it is done for the front installed
InsulGard, plug the cord from the power module into an outside 115 V AC
receptacle. Power and TR LED should be on. The modem is ready for
communication.