EATON ELECTRICAL
25
Predictive Diagnostics
2.2.3.2
Step 2 – Sensor and power connections
•
Connect coax cables to all PD sensors according to correspondent PD sensor
installation manual.
•
Connect a 3-conductor shielded cable to RTD terminals in a motor (or generator)
according to drawings and RTD type. If additional RTD was installed, connect its
leads to RTD cable using appropriate crimping tool. Label all conductors on both
ends. (Check IG documentation! RTD sensor may have been already installed in the
sensor interface board.)
•
Connect Current Sensor using appropriate crimping tool. Label positive polarity
terminal (+) or dot.
•
Connect Voltage Sensor. Label positive polarity terminal (+) or dot.
Note: Do not
connect to PT at this time.
•
Connect the humidity sensor according to its description. A humidity sensor has
three wires: +5 Volt, Ground, and Signal. Make sure that all wires are properly
labeled of both sides. (Check IG documentation! Humidity sensor may have been
already installed in the sensor interface board.)
•
Note: Do not connect 115/230 VAC power at this time
2.2.3.3
Step 3. - Connections to the device.
All signal connections inside the InsulGard enclosure are found on the Sensor Interface
Board shown in Figure 4. Connectors are in red on in the Figure 5.
WARNING: THIS MONITOR MUST BE INSTALLED AND SHOULD NOT
BE USED FOR ANY OTHER PURPOSE THAN WHAT IS DESCRIBED IN
THIS DOCUMENT. IF THIS DEVICE IS USED FOR ANY OTHER
PURPOSE, OR NOT INSTALLED PER INSTRUCTIONS IT MAY NOT
FUNCTION PROPERLY.