EATON ELECTRICAL
42
Predictive Diagnostics
3.2 Working with Data Memory
♦
InsulGard allows observing all stored information in the memory data.
♦
Press the
Memory
key to enter memory mode.
♦
Device will display
ALL-XXXXX
- total number of records in its memory.
♦
Press
Enter
key. The current month and date will be displayed.
♦
Change the date to the desirable and press
Enter
. The earliest record date and time
on this date will appear.
♦
Scroll records up and down by using
keys. Alarm LEDs will change their colors
correspondingly to alarm status obtained in the particular measurement.
♦
When the desired date and time is selected, press
Enter
.
01-XXX-Y (for PDI) or
01Q-XXX (for Q
02
)
will appear depending upon what parameter was chosen for alarm.
You can switch between PDI and Q
02
by
keys or between channels by
keys.
♦
The first two digits represent channel #, Q – magnitude parameter, XXX – parameter
percent of Red alarm, and Y – alarm code for the selected channel: 1 –
Good
(PD
characteristics are below Green threshold), 2 –
Good
(PD above Green but below
Yellow threshold), 3 –
Warning
(PD is above Yellow but below Red threshold), 4 –
Alarm
(PD is above Red threshold).