Predictive Diagnostics
Current - (
Fr08
)
Humidity - (
Fr09
) (Activate this option, if one of auxiliary channels is configured for humidity.)
Scroll setup parameters until
SET Shou
appears.
Press
Enter
.
dAtE-On(OFF)
will appear. Use
keys to select an item for display and activate
it setting ON.
When done, press
Enter
. See also
Setting Scrolling Time
.
Sensor Sensitivity:
InsulGard can use almost any PD sensor that is capable of operating in a radio-frequency band. Sensors
differ by their response to the same discharge event, in other words, by their sensitivity. In order to take
into account the specifics of a particular sensor, one should set proper sensitivity for every used sensor.
In general, sensor sensitivity should be determined from off line sensor calibration.
We recommend using the same sensitivity for all sensors of the same type and function.
Scroll setup parameters until
SEnSor
appears.
Press
Enter
.
C01-10.00
will appear. This represents the sensitivity of Channel 01 equal to 10.00
nC/Volt. Press
Enter
to set the selected channel. Use
keys to change sensitivity and/or
channel. It is better to be consistent when changing channels. Here is the recommended way to
change channels:
Press
Enter
when finished with selected channel. Using
to select another channel.
Press
Esc
when done with all channels.
Measurements Schedule:
Two modes of measurements are available. These are based on the time interval between consequent
measurements and on schedule. As default, the device is set to measure four times a day at 4:00AM,
10:00AM, 4:00PM, and 10:00PM. Up to 50 times per day can be set.
Scroll setup parameters until
trEAdinG
appears.
Press
Enter
.
rEG-dt
will appear. Use
keys to schedule the measurement by a time interval
rEG-dt
or a fixed time of a day
t rEG-t.
When done, press
Enter
.
Schedule by time interval:
Select
rEG-dt
and press
Enter
.
Set time interval in format XX.XX (hh.mm) using
keys. Military format (24 hour) is used.
Maximum interval can be 23 hours and 59 minutes.
Press
Enter
.
Schedule by fixed time of a day:
Select
rEG-t
and press
Enter.
t01-00.00
will appear.
Set t01 to a desired time in the (hh.mm) format using
keys.
When finished with t01, press
Enter.
Use
keys to select t02 to the desired time. Continue until the required number of daily
measurements specified.
When finished with all time settings, press
Esc
.
Note: Device will take the scheduled readings only until the time setting 00.00 is reached. When
00.00 is reached, device will start the next measurement at the time t01 on the next day.
Data Save Mode:
Single measurement data consist of PRPDD matrixes (one per active channel) and header containing
common and calculated data for all channels. Size of either one matrix or header is about 1kByte.
The device has 2Mbyte of data memory available. The memory can be conserved choosing appropriate
data saving mode. Matrixes should not be stored every time. Two data saving modes are available: FULL
(saving all the data including matrixes for every measurement) and BRIEF (saving header only and full
matrixes occasionally as preset).