36
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08
CAUTION
CABINET MAY FALL. Do not loosen the hardware attaching the front supports to the cabinet base. The cabinet
must be lowered by the jacking bolts before the supports can be removed.
10. Carefully and evenly
lower the cabinet by turning each jacking bolt consecutively two full turns
(maximum)
until the casters contact the floor and the cabinet is no longer supported by the jacking bolts.
11. After the IBC is resting on the floor, remove the jacking bolts and floor protectors. Recycle them in a
responsible manner.
12. Remove the cabinet support bolts fastening the left, right, front, and rear supports together (see
).
13. Remove the cabinet mounting bolts holding the left, right, front, and rear supports to the cabinet base (see
).
14. If a sidecar is installed to the IBC, proceed to
; otherwise, skip to
.
15. Remove the bottom screw securing the sidecar front panel. Lift the panel straight up to remove from the
panel hanger brackets at the top of the cabinet.
16. Remove the sidecar support bolts fastening the side support to the front and rear supports.
17. Remove the sidecar mounting bolts holding the front and rear sidecar supports to the cabinet base.
18. Remove the supports. If installing the cabinet permanently, retain the cabinet mounting bolts; otherwise,
recycle the bolts along with the support brackets in a responsible manner.
19. Close the door and secure the latch.
20. If the leveling feet are not retracted, turn all four leveling feet until they are retracted as far into the cabinet
as possible.
NOTE
The battery cabinet may be located to either the right or left of the UPS cabinet. The
recommended location is to the right of the UPS cabinet. This procedure assumes the
battery cabinet is located to the right of the UPS cabinet.
21. If line-up-and-match installation, remove the rectangular knockout on the bottom front side of the UPS and
the IBC (see
22. The IBC is shipped set up for rear ventilation with a cover plate installed over the ventilation grill on top of
the unit (see
). If top ventilation is required, remove the screws securing the plate at the top of
the unit and install the plate over the rear ventilation grill (see
).
CAUTION
To prevent tipping when rolling the cabinet, push the cabinet from the rear whenever possible.
23. Roll the IBC to the line-up-and-match installation location on the right side of the UPS cabinet making sure
the doors are flush with each other or to the standalone installation location.
NOTE
Use the leveling feet to level and lock the cabinet in place.
24. Secure the IBC in position by lowering the leveling feet until the cabinet is level and locked in place.
25. If permanently mounting the IBC, proceed to
; otherwise, skip to
26. Locate the two floor mounting brackets from the parts kit.
Содержание IBC-L
Страница 86: ...16400022808 164000228 08 ...