48
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08
Figure 24. IBC Bottom Entry Conduit and Wire Entry Locations
Bottom Entry Conduit
Landing for DC Output
(Remove panel to drill or
punch conduit holes.)
Figure 25. IBC Sidecar Top Entry Conduit and Wire Entry Locations
Sidecar Top Entry Conduit
Landing for DC Output
(Remove panel to drill or
punch conduit holes.)
44..44
B
Baatttteerryy B
Brreeaakkeerr IInnssttaannttaanneeoouuss TTrriipp S
Seettttiinngg
NOTE
The specified default instantaneous trip setting provides the maximum protection for
the batteries. Failure to adhere to 5x instantaneous trip setting voids the battery
warranty.
To verify the trip setting:
1.
Verify the UPS system is not in reserve mode or operating on battery. Refer to the applicable Eaton 93PM
UPS Installation and Operation manual, listed in paragraph
, for UPS operating
procedures.
2.
Verify the battery breaker instantaneous trip setting is set to 5 on all three trip dials (see
).
3.
If dials are not set to 5, set each to 5.
4.
Proceed to paragraph
Содержание IBC-L
Страница 86: ...16400022808 164000228 08 ...