74
Eaton 93PM Integrated Battery Cabinet (IBC-L, IBC-LH [432V], and IBC-LH [480V]) Installation Manual 164000228—Rev 08
77..22..22
EEnnvviirroonnm
meennttaall aanndd S
Saaffeettyy S
Sppeecciiffiiccaattiioonnss
Operating Temperature
The battery cabinet is rated for operation in up to a 40°C (104°F) ambient
temperature.
NOTE
Emergency lighting and power equipment battery cabinets (UL924) are rated
for operation in a 20°–30°C (68°–86°F) temperature environment.
The batteries are rated for a 25°C (77°F) ambient temperature to extend their useful
life.
Transit Temperature
-15°C to 40°C (5°F to 104°F)
Storage Temperature
IBC-L: -15°C to 40°C (5°F to 104°F)
IBC-LH: -15°C to 40°C (5°F to 104°F)
Operating Altitude
Maximum 1500m (5000 ft) at 40°C without derating
Transit Altitude
15000m (49213 ft)
Ventilation
Convection
Relative Humidity (operating and
storage)
95%, noncondensing
Acoustical Noise
Not applicable
Safety Conformance
UL1778 4
th
edition
Agency Markings
cULus
EMC (Class A)
FCC Part 15 Class A and 62040-2 c3