39
Figure 17. Top Ventilation
Cover
Ventilation
Plate
Grill
Top
View
Front
Back View
44..33
IInnssttaalllliinngg IIB
BC
C P
Poow
weerr W
Wiirriinngg
IBCs can be installed in a line-up-and-match configuration with the power wiring routed through the bottom of
the IBCs and UPS cabinet or in a standalone configuration with the power wiring routed between the IBCs and
the UPS cabinet using conduit. Use the appropriate procedure for the type of installation being wired.
44..33..11
LLiinnee--U
Upp--aanndd--M
Maattcchh P
Poow
weerr W
Wiirriinngg
NOTE 1
All battery cabinets will be directly connected to the UPS and not daisy-chained between
each cabinet. All power wiring between the IBCs and the UPS is factory supplied.
NOTE 2
Up to four IBCs can be installed in a line-up-and-match configuration.
NOTE 3
If installing three or four IBCs, longer battery power cables are packed with IBC 3 and
IBC 4. Ensure the longer cables are used to wire IBC 3 and IBC 4.
Use this procedure to wire line-up-and-match 93PM Integrated Battery Cabinets to the 93PM UPS cabinet.
To install wiring to connections:
1.
Verify the UPS system is turned off and all power sources are removed. Refer to the applicable Eaton
93PM UPS Installation and Operation manual, listed in paragraph
, for UPS
operating procedures.
2.
Open the front door by lifting the latch from the bottom and turning to the right (counterclockwise) and
swing the door open.