4.1.2 Connection possibilities and ranges
Cubicles with an incoming or one outgoing feeder
There are various possibilities for the connection of these
groups:
•
Connection using cable-lugs, maximum of two per
phase, with the exception of 630 A equipment for which
a connection-set has been developed for three cables
per phase (copper).
•
Using cable-clamping blocks on switches exceeding
1000 A, for one or more cables.
•
A connection-set is also available on request for
switches exceeding 1000 A, for five cables per phase
maximum of 240 mm
2
(copper).
Compartments with draw-out units
Draw-out units are connected to the main connection-
block. Main connection-blocks have the following
connection ranges:
•
160 A: 2,5 -95 mm
2
, Cu
•
250 A: 35 -150 mm
2
, Cu
•
315 A: 50 - 1 x 240 mm
2
, Cu
•
400 A: 50 - 2 x 240 mm
2
, Cu
•
630 A: 50 - 2 x 240 mm
2
, Cu
Remarks
•
In order to achieve good connection when using 2.5
mm
2
solid wire, the bare conductor must be bent
double for each connection to the main connection-
block.
•
When connecting twined cables upto 16 mm
2
to the
main connection-block, it is advisable to use cable- end
sleeves.
•
All 160 A draw-out units, 2 x 125 mm high and larger,
may, on request, be supplied with terminals for
optimum connection of 2 x 95 mm
2
(copper).
•
When two or three draw-out units are placed next to
each other in one compartment, connection is made to
terminals located in the cable-compartment 1). The
connection range of the respective terminals is:
- main current, maximum 10 mm
2
- auxiliary current, maximum 2.5 mm
2
•
A maximum of twenty 2.5 mm
2
leads may be connected
to the auxiliary connection-block.
Miscellaneous equipment
Fuse links
DIN 00: cables up to 95 mm
2
(copper). For cables with
solid cores up to 4 mm
2
and stranded cores up to 10 mm
2
the use of cable-end sleeves is recommended.
DIN 0: connection-bolt
M8
DIN 1: connection-bolt
M10
DIN 2: connection-bolt
M10
DIN 3: connection-bolt
M10
DIN 4: connection-bolt
M16
When connecting cables it should be ensured that the
connection-strips are not bent due to inexpert connection of
cables.
Load break switches
Duco/Dumeco 40-63 A:
•
solid 2.5-25 mm
2
•
plaited and flexible
- without core-end sleeves 4-25 mm
2
- with core-end sleeves 1.5-2.5 mm
2
Dumeco 125 A
•
solid 6-70 mm
2
•
stranded
- without core-end sleeve 16-70 mm
2
- with core-end sleeve 6-10 mm
2
•
flexible
- without core-end sleeve 16-50 mm
2
- with core-end sleeve 6-10 mm
2
Load break switches
Dumeco 200 A: connection-bolt M8
Dumeco 315 A: connection-bolt M10
Dumeco 400 A: connection-bolt M10
Dumeco 800 A: connection-bolt M12
Dumeco 1000 A: connection-bolt M16
Dumeco 1600 A: connection-bolts 2 x M12
Dumeco 2500 A: connection-bolts 4 x M12
Dumeco 3150 A: connection-bolts 4 x M12
Dumeco 3600 A: connection-bolts 4 x M12
Fuse switches
Vemeco 100 A: connection-bolt M8
Vemeco 160 A: connection-bolt M8
Vemeco 250 A: connection-bolt M10
Vemeco 400 A: connection-bolt M10
Vemeco 630 A: connection-bolt M10
Содержание Holec Capitole 40
Страница 2: ...Administrative data Issue number G01 002 Date of issue 30 09 2008...
Страница 62: ...Capitole 40 62 1991 901 G01 002 Place the draw out units into position Figure 3 35...
Страница 74: ...Capitole 40 74 1991 901 G01 002 Figure 4 1...
Страница 76: ...Capitole 40 76 1991 901 G01 002 Figure 4 2...
Страница 78: ...Capitole 40 78 1991 901 G01 002 Figure 4 3...
Страница 82: ...Capitole 40 82 1991 901 G01 002 Figure 4 5 Figure 4 6...
Страница 84: ...Capitole 40 84 1991 901 G01 002 Figure 4 7...
Страница 86: ...Capitole 40 86 1991 901 G01 002 Figure 4 8...
Страница 88: ...Capitole 40 88 1991 901 G01 002 Figure 4 9...
Страница 90: ...Capitole 40 90 1991 901 G01 002 Figure 4 10...
Страница 92: ...Capitole 40 92 1991 901 G01 002 Figure 4 11...
Страница 94: ...Capitole 40 94 1991 901 G01 002 Figure 4 12...
Страница 96: ...Capitole 40 96 1991 901 G01 002 Figure 4 13...
Страница 97: ...Capitole 40 1991 901 G01 002 97 APPENDIX 1 EU DECLARATION OF CONFORMITY...
Страница 98: ...Capitole 40 98 1991 901 G01 002 APPENDIX 2 KEMA TEST REPORT...
Страница 99: ...Capitole 40 1991 901 G01 002 99...
Страница 100: ...Capitole 40 100 1991 901 G01 002 APPENDIX 3 LLOYD S CERTIFICATE...
Страница 101: ...Capitole 40 1991 901 G01 002 101...