Emergency On Call Service: Local representative (http://www.eaton.com/moeller/aftersales) or +49 (0) 180 5 223822 (de,en)

V Function diagrams

                                                     English 

a) ON-delayed over- and undervoltage monitoring,  

1 x 2 c/o contacts

b) OFF-delayed over- and undervoltage monitoring,  

1 x 2 c/o contacts

c) ON-delayed over- and undervoltage monitoring,  

2 x 1 c/o contact

d) OFF-delayed over- and undervoltage monitoring,  

2 x 1 c/o contact

e) ON-delayed phase unbalance monitoring
f)  OFF-delayed phase unbalance monitoring
g) Phase sequence and phase failure monitoring
h) Automatic phase sequence correction

  Control supply voltage / Three-phase measuring voltage

 Threshold value

 Measured value

 Threshold value

  Output relays 1 

 

Output relay 2

 

Red LED

 

 Red LED

 Yellow LED

  Start-up delay t

S

, fixed

  Tripping delay tv, adjustable 

  Start-up delay t

S1

 of R1, fixed 

  Start-up delay t

S2

 of R2, fixed

Threshold values for over- and undervoltage

EMR5-AWN280-1:

   L1-L2-L3-N  180-280 V  U

min

 = 180-220 

 

 

 

U

max

 = 240-280 V

EMR5-AWN500-1:

 L1-L2-L3 

300-500 

V  U

min

 = 300-380 

V

 

 

 

U

max

 = 420-500 V 

EMR5-AWM580-2:

 L1-L2-L3 

350-580 V  U

min

 = 350-460 

 

 

 

U

max

 = 480-580 V

EMR5-AWM720-2:

 L1-L2-L3 

450-720 V  U

min

 = 450-570 

 

 

 

U

max

 = 600-720 V

EMR5-AWM820-2:

 L1-L2-L3 

530-820 V  U

min

 = 530-660 

 

 

 

U

max

 = 690-820 V

 

Threshold values for phase unbalance

Switch-off value:    
L1-L2-L3:  2-25 % (unbalance value in percentage)

Unbalance value in percentage = 

 Max. difference_L1,L2,L3  

*

100 %

 

  Average value_L1,L2,L3

Switch-on value: 
Set switch-off value -20%

Operating principle                                                      

EMR5-AW are multifunctional monitoring relays for three-phase 
mains. They monitor all phase parameters such as phase sequence, 
phase failure, over- and undervoltage and phase unbalance. 

 

EMR5-AWN280-1 is also suitable for monitoring single-phase mains 
(see ‚Electrical connection‘).

Over- and undervoltage, 1 x 2 c/o contacts

If all three phases are present with correct voltage, the output 
relays are energized. If the voltage to be monitored exceeds or 
falls below the set threshold value, the output relays de-energize 
instantaneously or delayed (0.1-30 s), depending on the set time 
delay. The fault type is indicated by LEDs. The output relays re-

energize automatically, instantaneously or with delay (0.1-30 s), 
depending on the set time delay, as soon as the voltage returns to 
the tolerance range, taking into account a fixed hysteresis of 5 %. 

Over- and undervoltage, 2 x 1 c/o contact

If all three phases are present with correct voltage, the output re-
lays are energized. If the voltage to be monitored exceeds the set 
threshold value, output relay R1 de-energizes instantaneously or 
delayed (0.1-30 s), depending on the set time delay. If the voltage 
to be monitored falls below the set threshold value, output relay 
R2 de-energizes instantaneously or delayed (0.1-30 s), depending 
on the set time delay. The fault type is indicated by LEDs. The 
output relays re-energize automatically, instantaneously or with 
delay (0.1-30 s), depending on the set time delay, as soon as the 

voltage returns to the tolerance range, taking into account a fixed 

hysteresis of 5 %. 

Phase unbalance

If all three phases are present with correct voltage, the output 
relays are energized. If the phase unbalance of the phases to 
be monitored exceeds the set unbalance threshold value, the 
output relays de-energize instantaneously or delayed (0.1-30 
s), depending on the set time delay. The fault type is indicated 
by LEDs. The output relays re-energize, instantaneously or with 
delay (0.1-30 s), depending on the set time delay, as soon as the 

voltage returns to the tolerance range, taking into account a fixed 

hysteresis of 20 %. 

Phase sequence and phase failure

If all three phases are present with correct phase sequence, the 
output relays are energized. They de-energize immediately if a 
phase failure or a phase sequence error occurs. The fault type is 
indicated by LEDs. The output relays re-energize automatically as 
soon as the voltage returns to the tolerance range. 

Automatic phase sequence correction

Applying control supply voltage / three-phase measuring voltage 
with correct phase sequence, energizes output relay R2 when the 
fixed start-up delay t

S2

 of about 200 ms is complete. Relay R2 

remains de-energized if the phase sequence is incorrect. 
If all three phases are present with correct voltage, output relay 
R1 energizes when the fixed start-up delay t

S1

 of about 250 ms is 

complete. If the voltage to be monitored exceeds or falls below the 
set threshold values for phase unbalance, over- or undervoltage 
or if a phase failure occurs, output relay R1 de-energizes. 

  

Output relay R2 is responsive only to a false phase sequence. In 
conjunction with a reversing contactor combination, this enables 
an automatic correction of the rotation direction (see circuit 
diagram on page 10).

The operating mode ‚Automatic phase sequence correction‘ 

can be selected only when ‚Phase sequence monitoring 
activated‘ (DIP2: OFF) and ‚2 x 1 c/o contact‘ (DIP3: ON) is 
selected. 

With the operating mode ‚Automatic phase sequence 
correction‘, the phase sequence error has the lowest error 
priority for the status indication. 

Содержание EMR5-AWM580-2

Страница 1: ...euvent pas non plus tenir compte de tous les cas d application Toutes les indications ne sont données qu à titre de description du produit et ne constituent aucunes obligations légales Pour de plus amples informations veuillez vous référer aux catalogues et aux fiches techniques des produits à votre agence Eaton ou à notre site http www eaton com moellerproducts Sous réserve de modifications techniq...

Страница 2: ...produit E Fijar el producto I Montare il prodotto D Produkt entfernen GB Remove product F Démontage du produit E Desmontar el producto I Rimuovere il prodotto 2CDC 252 282 F0005 2CDC 252 281 F0005 7 mm 0 28 in 7 mm 0 28 in 7 mm 0 28 in 2 x 0 5 4 mm 2 x 20 12 AWG Ø 4 5 mm 0 177 in PH 1 0 6 0 8 Nm 5 31 7 08 lb in 2 x 0 75 2 5 mm 2 x 18 14 AWG 2 x 0 75 2 5 mm 2 x 18 14 AWG 2CDC 252 047 F0b09 4 2 3 I ...

Страница 3: ...elais 1 25 26 28 Ausgangsrelais 2 EMR5 AWN280 1 eignet sich auch zur Überwachung von Einphasennetzen Voraussetzungen DIP 2 ON und L1 L2 L3 gebrückt Schwellwert für Asymmetrie auf Maximum 25 eingestellt Fehlermeldungen Überspannung F1 an Unterspannung F2 an Asymmetrie F1 und F2 an Phasenausfall F1 an F2 blinkend Phasenfolge F1 und F2 abwechselnd blinkend Neutralleiterbruch F1 an F2 blinkend Schwell...

Страница 4: ...voltage In case of other faults both output relays react synchronously I Face avant et dispositifs de commande Français Indication de fonctionnement par LED R T LED jaune Indication relais et temporisation V Relais activé W Temporisation en cours F1 LED rouge Message de défaut F2 LED rouge Message de défaut Réglage de la valeur de seuil de surtension Réglage de la valeur de seuil de sous tension R...

Страница 5: ...ensión relé de salida R2 reacciona ante una subtensión En el caso de otros fallos los dos relés de salida reaccionan sincrónicamente I Vista frontale con gli elementi di comando Italiano LED di visualizzazione dello stato di funzionamento R T LED giallo Indicazione relè e temporizzazione V Relè eccitato W Temporizzazione in corso F1 LED rosso Messaggio di errore F2 LED rosso Messaggio di errore Im...

Страница 6: ...e Spannung den eingestellten Schwellwert so fällt Ausgangsrelais R1 je nach eingestellter Verzögerungsart unverzögert oder verzö gert 0 1 30 s ab Unterschreitet die zu überwachende Spannung den eingestellten Schwellwert so fällt Ausgangsrelais R2 je nach eingestellter Verzögerungsart unverzögert oder verzögert 0 1 30 s ab Die Fehlerart wird durch LEDs angezeigt Die Ausgangsrelais ziehen automatisc...

Страница 7: ...Unbalance Hyst Unbalance Hyst Unbalance ts start up delay fixed 200 ms tv adjustable tripping delay f OFF delayed phase unbalance monitoring 25 26 25 28 L1 L2 L3 15 16 15 18 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L2 L3 L1 L3 L2 L1 L2 L1 L3 L2 L3 t s 2CDC 252 094 F0207 F1 red LED F2 red LED R T yellow LED Measuring value ts start up delay fixed 200 ms g Phase sequence and phase failure monitoring L1 L2 L3 1...

Страница 8: ...olgekorrektur Automatic phase sequence correction Correction automatique de l ordre des phases Corrección automática de la secuencia de fases Correzione automatica della sequenza fasi Die Unterbrechung des Neutralleiters im zu überwachenden Netz wird mittels Asymmetrieauswertung erkannt Bei unbelastetem Neutralleiter d h symmetrischer Last zwischen allen drei Phasen kann ein Neutralleiterbruch eve...

Страница 9: ...s are energized If the voltage to be monitored exceeds the set threshold value output relay R1 de energizes instantaneously or delayed 0 1 30 s depending on the set time delay If the voltage to be monitored falls below the set threshold value output relay R2 de energizes instantaneously or delayed 0 1 30 s depending on the set time delay The fault type is indicated by LEDs The output relays re ene...

Страница 10: ...les relais de sortie sont activés Si la tension à surveiller dépasse la valeur de seuil ajustée le relais de sortie R1 se désactive selon la temporisation sélectionnée sans temporisation ou avec temporisation 0 1 30 s Si la tension à surveiller chute en dessous delavaleurdeseuilajustée lerelaisdesortieR2sedésactive selonla temporisation sélectionnée avec 0 1 30 s ou sans temporisation Le type d er...

Страница 11: ...ada excede el valor umbral ajustado el relé de salida R1 se des energiza instantáneamente o con retardo 0 1 30 s dependiendo del tiempo ajustado Si la tensión monitorizada cae por debajo del valor umbral ajustado el relé de salida R2 se des energiza instantáneamente o con retardo 0 1 30 s dependiendo del tiempo ajustado El tipo de fallo se indica mediante los LEDs Los relés de salida se re energiz...

Страница 12: ...sta a misura aumenta oltre il valore di soglia impostato il relè di uscita R1 si diseccita a seconda del modo di ritardo impostato senza o con 0 1 30 s ritardo Se la tensione sottoposta a misura diminuisce oltre il valore di soglia impostato il relè di uscita R2 si diseccita a seconda del modo di ritardo impostato senza o con 0 1 30 s ritardo Il tipo di errore viene visualizzato via LED I relè di ...

Отзывы: