Installation and user manual for the  

BiWire / Conventional Repeater  

  

• 

Once the cable entry holes have been cut then fit the cable 

glands to the back box .

• 

If the panel is being flush mounted, then insert the panel into 

the recess feeding the cables through the rear cable entry 

points .

• 

If the panel is being wall mounted then cut out the required 

number of cable entry holes in the back using a 20mm hole 

saw with pilot drill bit as shown in Figure 19 . Fit the glands to 

the back box and pull through the required cables .

• 

Using the mounting holes in the back box, drill holes into the 

wall and insert wall plugs and secure the panel to the wall as 

shown in Figure 20 . Ensure any dust is cleaned from the back 

box .

• 

Secure the PSE PCB back into the back box by following the 

reverse instructions in Figure 18 .

• 

Fit the PCB shelf and cables by following the reverse instruc-

tions in Figure 16 and Figure 17 on page 9 .

• 

If the panel is wall mounted, pull the cabling through the glands 

ready for wiring .

• 

Fit the door back onto the back box by following the reverse 

instructions in Figure 15 .

Figure 10. Cut cable entry holes

Figure 11. Secure the panel to the wall

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание EFBWCV-REPEATER

Страница 1: ...Technical Data PR216 219 508 01 Installation and user manual for the BiWire Conventional Repeater Panel EFBWCV REPEATER www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...t IE 3 Power Supply Equipment PSE 4 System Wiring 5 Status Indications 5 Repeater I O 7 Installation Instructions 8 Before you begin 8 Panel Installation 9 Installation Testing 14 Operating Instructio...

Страница 3: ...erate within their speci fication when the environmental conditions outside the cabinet of the IE PSE comply with class 3k5 of EN 60721 3 3 1995 The BiWire Conventional Repeater Panel The BiWire Conve...

Страница 4: ...page 16 provides a full technical specification for the power supply Note that the charging circuit will be in its high impedance state approximately 3V DC if no batteries faulty batteries or only one...

Страница 5: ...supplies the only wiring that is required is the mains input to the power supply unit and the data cable between the Fire Panel and each repeater panel as illustrated in Figure 3 Figure 3 System Wiri...

Страница 6: ...y Failure ON SLOW SLOW Battery impedance fault Charger Fault ON ON SLOW Charger voltage fault Sounder Fault ON SLOW SLOW Short or open circuit condition on the sounder circuit FRE Fault ON SLOW SLOW S...

Страница 7: ...anel will briefly flash the Zone Fault indicators to show the number of repeaters it has found Below is a table of what these indications mean It is important to note this during installation to ensur...

Страница 8: ...SYSTEM DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE TERMINAL BLOCKS NOTE INSTALLATION MAINTENANCE MUST BE PERFORMED BY AN APPROPRIATELY QUALIFIED PERSON THE EQUIPMENT CARRIES NO WARRANTY UNLESS THE...

Страница 9: ...ENTRANCE Mounting the Panel To prepare the panel for mounting you need to remove the front cover of the panel and the PCB shelf and the PSE from the back box To remove the front cover of the panel un...

Страница 10: ...ack box and pull through the required cables Using the mounting holes in the back box drill holes into the wall and insert wall plugs and secure the panel to the wall as shown in Figure 20 Ensure any...

Страница 11: ...ns NOTES OBEY VOLT DROP LIMITATION WHEN SIZING CABLES USE ONLY APPROVED CABLE TYPES DO NOT TIGHTEN TERMINAL CONNECTOR SCREWS TOO TIGHT KEEP POLARITY THROUGHOUT NON COLOURED CONDUCTORS SHOULD BE PERMAN...

Страница 12: ...shown as grey 3 Connect the link cable between the two remaining terminals CAUTION DO NOT USE A HIGH VOLTAGE TESTER WHEN WIRING IS CONNECTED TO ANY ELECTRONIC EQUIPMENT NOTE IT IS IMPORTANT THAT ZONE...

Страница 13: ...the cable to the Repeater I O terminals on the Repeater Panel see Figure 15 observing correct polarity to to When daisy chaining repeater panels together simply connect another twisted pair cable betw...

Страница 14: ...H SHORT CIRCUIT FAULTS ON ZONES AS THE PTC FUSE NEEDS TIME TO RECOVER IF IT HAS TRIPPED Repeater Check Place an individual zone into Zone Test Mode on the Fire Panel see Fire Panel manual for further...

Страница 15: ...zzer button To silence the panel s internal buzzer at access level 2 enter the code 3112 and then press the Mute Buzzer button This will only silence the buzzer of the repeater and not the Fire Panel...

Страница 16: ...Cable Type Cable type 2 core 1 5mm 2 screened fire rated cable twisted pair 500m max Compliance Compliance to Standards BS5839 part1 PSE Specification EFBWCV REPEATER Power Specification Mains Voltag...

Страница 17: ...Technical Data PR216 219 508 01 Effective March 2017 Installation and user manual for the BiWire Conventional Repeater Manufacturers Contact Details www acornfiresecurity com www acornfiresecurity co...

Отзывы: