background image

3

Technical Data 

PR216-219-508-01

Effective March 2017

Installation and user manual for the  

BiWire / Conventional Repeater  

  

Introduction

Purpose

This manual is intended as a guide for the installation and commis-

sioning of the BiWire / Conventional Repeater panel . The content 

of this guide is intended to assist the user to install a fire alarm 

system and does not specify the detailed design of the product . 

The guide assumes a reasonable level of competency with this 

type of system .
The installation of this system can only be carried out by a compe-

tent person with relevant current training and experience, with 

access to requisite tools, equipment and information (as stipulated 

by BS5839) .
The design has been carried out in accordance with a quality 

management system, which incorporates a set of rules for the 

design of all elements of the Indication Equipment (IE) and Power 

Supply Equipment (PSE) .
The components of the IE and PSE have been selected for the 

intended purpose, and are expected to operate within their speci-

fication when the environmental conditions outside the cabinet of 

the IE / PSE comply with class 3k5 of EN 60721-3-3:1995 . 

 

 

 

The BiWire/Conventional Repeater Panel

The BiWire/Conventional Repeater Panel mimics the visual and 

audible indications of the Fire panel it is connected to . This is a 

purely passive repeater panel so it is not possible to send instruc-

tions to the Fire panel to perform actions such as Sound Alarms, 

Silence Alarms, or Reset . Each repeater panel comes with an 

integral power supply and battery backup so there is no power 

requirements from the main Fire panel .

Indication Equipment (IE)

The panel enclosure is constructed from PC ABS components . 

The front cover is hinged at the bottom and is secured at the top 

of the panel by two retaining screws . On the in-side of the panel a 

sliding PCB tray makes it easy to remove the tray without touching 

the PCB . The back box houses the PSE, the stand-by batteries and 

has 29 x 20mm cable access points . Terminal blocks are positioned 

to enable ease of connection . Figure 1 shows the dimensions of 

the panel .

Figure 1. BiWire/Coventional Repeater Panel Dimensions

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание EFBWCV-REPEATER

Страница 1: ...Technical Data PR216 219 508 01 Installation and user manual for the BiWire Conventional Repeater Panel EFBWCV REPEATER www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...t IE 3 Power Supply Equipment PSE 4 System Wiring 5 Status Indications 5 Repeater I O 7 Installation Instructions 8 Before you begin 8 Panel Installation 9 Installation Testing 14 Operating Instructio...

Страница 3: ...erate within their speci fication when the environmental conditions outside the cabinet of the IE PSE comply with class 3k5 of EN 60721 3 3 1995 The BiWire Conventional Repeater Panel The BiWire Conve...

Страница 4: ...page 16 provides a full technical specification for the power supply Note that the charging circuit will be in its high impedance state approximately 3V DC if no batteries faulty batteries or only one...

Страница 5: ...supplies the only wiring that is required is the mains input to the power supply unit and the data cable between the Fire Panel and each repeater panel as illustrated in Figure 3 Figure 3 System Wiri...

Страница 6: ...y Failure ON SLOW SLOW Battery impedance fault Charger Fault ON ON SLOW Charger voltage fault Sounder Fault ON SLOW SLOW Short or open circuit condition on the sounder circuit FRE Fault ON SLOW SLOW S...

Страница 7: ...anel will briefly flash the Zone Fault indicators to show the number of repeaters it has found Below is a table of what these indications mean It is important to note this during installation to ensur...

Страница 8: ...SYSTEM DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE TERMINAL BLOCKS NOTE INSTALLATION MAINTENANCE MUST BE PERFORMED BY AN APPROPRIATELY QUALIFIED PERSON THE EQUIPMENT CARRIES NO WARRANTY UNLESS THE...

Страница 9: ...ENTRANCE Mounting the Panel To prepare the panel for mounting you need to remove the front cover of the panel and the PCB shelf and the PSE from the back box To remove the front cover of the panel un...

Страница 10: ...ack box and pull through the required cables Using the mounting holes in the back box drill holes into the wall and insert wall plugs and secure the panel to the wall as shown in Figure 20 Ensure any...

Страница 11: ...ns NOTES OBEY VOLT DROP LIMITATION WHEN SIZING CABLES USE ONLY APPROVED CABLE TYPES DO NOT TIGHTEN TERMINAL CONNECTOR SCREWS TOO TIGHT KEEP POLARITY THROUGHOUT NON COLOURED CONDUCTORS SHOULD BE PERMAN...

Страница 12: ...shown as grey 3 Connect the link cable between the two remaining terminals CAUTION DO NOT USE A HIGH VOLTAGE TESTER WHEN WIRING IS CONNECTED TO ANY ELECTRONIC EQUIPMENT NOTE IT IS IMPORTANT THAT ZONE...

Страница 13: ...the cable to the Repeater I O terminals on the Repeater Panel see Figure 15 observing correct polarity to to When daisy chaining repeater panels together simply connect another twisted pair cable betw...

Страница 14: ...H SHORT CIRCUIT FAULTS ON ZONES AS THE PTC FUSE NEEDS TIME TO RECOVER IF IT HAS TRIPPED Repeater Check Place an individual zone into Zone Test Mode on the Fire Panel see Fire Panel manual for further...

Страница 15: ...zzer button To silence the panel s internal buzzer at access level 2 enter the code 3112 and then press the Mute Buzzer button This will only silence the buzzer of the repeater and not the Fire Panel...

Страница 16: ...Cable Type Cable type 2 core 1 5mm 2 screened fire rated cable twisted pair 500m max Compliance Compliance to Standards BS5839 part1 PSE Specification EFBWCV REPEATER Power Specification Mains Voltag...

Страница 17: ...Technical Data PR216 219 508 01 Effective March 2017 Installation and user manual for the BiWire Conventional Repeater Manufacturers Contact Details www acornfiresecurity com www acornfiresecurity co...

Отзывы: