15
Technical Data
PR216-219-508-01
Effective March 2017
Installation and user manual for the
BiWire / Conventional Repeater
Operating Instructions
Multi-Function Buttons
The numerical value in the centre of the button is used to enter
access codes for level 2 .
Mute Buzzer
This function is available at access level 1 and 2 .
•
To silence the panel’s internal buzzer at access level 1 just press
the
Mute Buzzer
button .
•
To silence the panel’s internal buzzer at access level 2 enter the
code 3112 and then press the
Mute Buzzer
button .
•
This will only silence the buzzer of the repeater and not the Fire
Panel
This function will immediately exit back to Access Level 1 .
Lamp Test
This function is available at access level 2 .
•
Enter the access code 3112 .
•
Press
Indicator Test
button
③
.
•
Each indicator on the front of the panel will turn on in turn and
then turn off in turn (excluding the Power On indicator) .
This function will immediately exit back to Access Level 1 .