background image

4

Technical Data 

 PR216-219-508-01

Effective March 2017

Installation and user manual for the  

BiWire / Conventional Repeater  

  

Power Supply Equipment (PSE)

The PSE has been specifically designed to operate the panel and 

may not be substituted for any other power source . The PSE is a 

Switch Mode Power Supply located within the cabinet as shown 

below . A dedicated 230V AC mains supply is required as the 

primary source; the supply is fused on the PCB by a 10 amp anti-

surge fuse . In the event of mains failure the PSE will automatically 

switched over to the standby battery power source until the main 

power source is restored .
The PSE maintains the charge for the two 12V 5Ah sealed lead 

acid batteries in a fully charged state . On initial power up the 

batteries will charge over a 24 hour period . Dependent on the 

charge of the installed battery the system may initially show a 

charger or battery fault .
The supply should be clearly labelled ‘FIRE ALARM: DO NOT 

SWITCH OFF’ at all isolation points .
PSE faults originating from the following are indicated by the panel 

using a dedicated repeater power fault indicator: 

• 

The loss of either power source

• 

Failure of the charger circuit

• 

High internal resistance of the battery

Figure 2 shows the location of the power supply . “PSE 

Specification” on page 16 provides a full technical specification for 

the power supply .
Note that the charging circuit will be in its high impedance state 

(approximately 3V DC) if no batteries, faulty batteries, or only one 

battery is connected . The full 27V DC (nominal) charging voltage 

should be present if the correct batteries are connected .
In order to test for correct operation of the batteries, remove the 

mains 230V AC fuse and allow the batteries to settle from their 

charging voltage for approximately 5 minutes . The battery voltage 

should then be measured using an electronic test meter and a 

voltage greater than 24V DC should be present .

Figure 2.  Power Supply Equipment

BATTERY DISPOSAL INSTRUCTIONS

   WARNING

RISK OF EXPLOSION IF BATTERY IS REPLACED BY AN 

INCORRECT TYPE

This product contains batteries and they must be disposed of in 

accordance with current waste disposal and pollution legislation 

and in particular The Environmental Protection Act 1990, Special 

Waste Regulation 1996 . It is recommended that the following 

authorities are contacted before any attempt is made to dispose 

of batteries; Environment Agency Local office, Local Authority 

Environmental Health or Waste Handling department .
The batteries and fire panel comply with WEEE 

disposal regulations . Do not dispose in general indus-

trial or household waste . Return unwanted products to 

a designated collection point for waste electrical and 

electronic equipment recycling .

www.acornfiresecurity.com

www.acornfiresecurity.com

Содержание EFBWCV-REPEATER

Страница 1: ...Technical Data PR216 219 508 01 Installation and user manual for the BiWire Conventional Repeater Panel EFBWCV REPEATER www acornfiresecurity com www acornfiresecurity com...

Страница 2: ...t IE 3 Power Supply Equipment PSE 4 System Wiring 5 Status Indications 5 Repeater I O 7 Installation Instructions 8 Before you begin 8 Panel Installation 9 Installation Testing 14 Operating Instructio...

Страница 3: ...erate within their speci fication when the environmental conditions outside the cabinet of the IE PSE comply with class 3k5 of EN 60721 3 3 1995 The BiWire Conventional Repeater Panel The BiWire Conve...

Страница 4: ...page 16 provides a full technical specification for the power supply Note that the charging circuit will be in its high impedance state approximately 3V DC if no batteries faulty batteries or only one...

Страница 5: ...supplies the only wiring that is required is the mains input to the power supply unit and the data cable between the Fire Panel and each repeater panel as illustrated in Figure 3 Figure 3 System Wiri...

Страница 6: ...y Failure ON SLOW SLOW Battery impedance fault Charger Fault ON ON SLOW Charger voltage fault Sounder Fault ON SLOW SLOW Short or open circuit condition on the sounder circuit FRE Fault ON SLOW SLOW S...

Страница 7: ...anel will briefly flash the Zone Fault indicators to show the number of repeaters it has found Below is a table of what these indications mean It is important to note this during installation to ensur...

Страница 8: ...SYSTEM DO NOT USE EXCESSIVE FORCE WHEN TIGHTENING THE TERMINAL BLOCKS NOTE INSTALLATION MAINTENANCE MUST BE PERFORMED BY AN APPROPRIATELY QUALIFIED PERSON THE EQUIPMENT CARRIES NO WARRANTY UNLESS THE...

Страница 9: ...ENTRANCE Mounting the Panel To prepare the panel for mounting you need to remove the front cover of the panel and the PCB shelf and the PSE from the back box To remove the front cover of the panel un...

Страница 10: ...ack box and pull through the required cables Using the mounting holes in the back box drill holes into the wall and insert wall plugs and secure the panel to the wall as shown in Figure 20 Ensure any...

Страница 11: ...ns NOTES OBEY VOLT DROP LIMITATION WHEN SIZING CABLES USE ONLY APPROVED CABLE TYPES DO NOT TIGHTEN TERMINAL CONNECTOR SCREWS TOO TIGHT KEEP POLARITY THROUGHOUT NON COLOURED CONDUCTORS SHOULD BE PERMAN...

Страница 12: ...shown as grey 3 Connect the link cable between the two remaining terminals CAUTION DO NOT USE A HIGH VOLTAGE TESTER WHEN WIRING IS CONNECTED TO ANY ELECTRONIC EQUIPMENT NOTE IT IS IMPORTANT THAT ZONE...

Страница 13: ...the cable to the Repeater I O terminals on the Repeater Panel see Figure 15 observing correct polarity to to When daisy chaining repeater panels together simply connect another twisted pair cable betw...

Страница 14: ...H SHORT CIRCUIT FAULTS ON ZONES AS THE PTC FUSE NEEDS TIME TO RECOVER IF IT HAS TRIPPED Repeater Check Place an individual zone into Zone Test Mode on the Fire Panel see Fire Panel manual for further...

Страница 15: ...zzer button To silence the panel s internal buzzer at access level 2 enter the code 3112 and then press the Mute Buzzer button This will only silence the buzzer of the repeater and not the Fire Panel...

Страница 16: ...Cable Type Cable type 2 core 1 5mm 2 screened fire rated cable twisted pair 500m max Compliance Compliance to Standards BS5839 part1 PSE Specification EFBWCV REPEATER Power Specification Mains Voltag...

Страница 17: ...Technical Data PR216 219 508 01 Effective March 2017 Installation and user manual for the BiWire Conventional Repeater Manufacturers Contact Details www acornfiresecurity com www acornfiresecurity co...

Отзывы: