Read image data
69
09/10 MN05013007Z-EN
Auxiliary relay (marker), digital outputs, text display
The following command will read the logical state of all
markers M1 to M16, digital outputs Q1 to Q8, text display
markers D1 to D8.
Telegram structure
Byte
Meaning
Value (hex), sent by
Bit
M
S
Master
Slave
7 6 5 4 3 2 1 0
Attribute ID
Read
5F
–
0 1 0 1 1 1 1 1
0
Response
Read successful
–
C2
1 1 0 0 0 0 1 0
Command
rejected
–
C0
1 1 0 0 0 0 0 0
0
1
Status of markers
M1 to M8
00
1
2
Status of markers
M9 to M16
00
2
3
Status of digital
outputs Q1 to Q8
00
3
4
Status of text
display markers D1
to D8
00
M
= master
S
= Slave
Содержание EASY222-DN