Read/write image data
111
09/10 MN05013007Z-EN
Example:
A voltage signal is present at analog input 1. The required
telegrams for reading the analog value are as follows:
Table 47:
Example telegram for reading the value at the analog
input “1”
Byte 4 – Data 1 (Low Byte): 4B
hex
Byte 5 – Data 2 (High Byte): 03
hex
l
corresponding 16-bit value: 034B
hex
= 843
The value 843 corresponds to the 10 bit value of the analog
converter. The following conversion is required for the actual
analog value:
Byte
Meaning
Value (hex), sent by
Master
Slave
Master
Slave
Attribute ID: Read
88
–
0
Response: read
successful
–
C2
0
1
Len
02
02
1
2
Part no.
8C
8C
2
3
Index
02
1)
02
1)
3
4 Data
1
00
4B
4
5
Data 2
00
03
5
6
Data 3
00
00
6
7
Data 4
00
00
1) 02 = Analog input I11
10 V
x
10 bit
=>
10 V
x
843 = 8.24 V
1023
1023