Read/write function blocks
97
09/10 MN05013007Z-EN
Setting the ON and OFF time (byte 2 to byte 5)
The table below shows which bytes precisely determine the
ON and OFF times of a channel. The resolution is in seconds.
Example:
Switch on time
Switch Off Time
bytes1
Byte 2
bytes3
bytes4
Minute
ON
Hour
ON
Minute
OFF
Hour
OFF
00 to 3B
hex
(00 to 59
dec
)
00 to 17
hex
(00 to 23
dec
)
00 to 3B
hex
(00 to 59
dec
)
00 to 17
hex
(00 to 23
dec
)
h
You must convert all decimals into hexadecimal values
and enter them accordingly.
Description
Instruction/byte
Value
Data of channel A of switching timer 4:
Attribute ID
1E
hex
Day: Monday through Saturday
The channel appears in the parameter menu
Byte 0
31
hex
(see above)
ON 19:00
bytes1
00
hex
Byte 2
13
hex
OFF: 06:30
bytes3
1E
hex
bytes4
06
hex