Read/write image data
109
09/10 MN05013007Z-EN
Local inputs: I1 – I16
This command string enables you to read the local inputs of
the easy700 basic unit. The relevant input word is stored in
Intel format.
Telegram structure
Table 46:
Byte 3 to 4 (master) or Byte 4 to 5 (slave):
Data 1 to 2
Byte
Meaning
Value (hex), sent by
Master
Slave
Master
Slave
Attribute ID: Read
88
–
0
Response:
Read successful
–
C2
Command
rejected
–
C0
1)
0
1
Len
02
02
1
2
Part no.
84
84
2
3
Index
00
00
3
4
Data 1 (Low Byte)
00
4
5
Data 2 (High Byte)
00
5 – 6
6 – 7
Data 3 – 4
00
00
1) Possible causes
Data 1 Bit 7
6
5
4
3
2
1
0
I1
0/1
I2
0/1
…
…
I8
0/1
Data 2 Bit 7
6
5
4
3
2
1
0
I9
0/1
I10
0/1
…
…
I16
0/1
Содержание EASY222-DN
Страница 10: ...Contents 6 09 10 MN05013007Z EN...
Страница 34: ...30 09 10 MN05013007Z EN...
Страница 258: ...254 09 10 MN05013007Z EN...
Страница 274: ...Glossary 270 09 10 MN05013007Z EN...
Страница 284: ...Alphabetical index 09 10 MN05013007Z EN 280...